Date Text
2001-08-31 00:00:00BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.CALL 233-5025 FOR MORE
 INFORMATION.
  
 AS PROVIDED FOR IN SBC 105.3 A RESIDENT
 INSPECTOR IS REQUIRED FOR A PROJECT OF
 THIS SCOPE.CONTACT DON NEELY AT
 561-659-8096 X 8333 FOR MORE
 INFORMATION.
  
 THIS PROPERTY IS IN A FLOOD ZONE AH BFE
 17.0' NGVD.
  
 THE FIRE PROTECTION PLANS MUST BE
 INCLUDED WITH THE PERMIT PLANS.SEE FS
 553.79 (2).
  
 THE LS PAGES DO NOT CLEARLY INDICATE THE
 LOCATION OF EXISTING OR PROPOSED NEW
 SMOKE BARRIER WALLS REQUIRED BY SBC 409.
 1.2.INCLUDE THE EXISTING PORTION OF
 THE BUILDING. DEMONSTRATE ALSO THE
 REMAINING REQUIREMENTS OF SBC 409.
  
 THE MAINTENANCE AND STORAGE ROOMS IN THE
 VICINITY OF GRID LINES F,3 ARE REQUIRED
 TO HAVE FIRE RATED SEPARATION FROM THE
 BUILDING BY SBC 409.1.5.
  
 SHEET S1 CITES ASCE 7-98.THE CITY IS
 CURRENTLY USING THE 1997 SBC WHICH
 INVOKES ASCE 7-95.FURTHER THE
 OCCUPANCY CLASSIFICATION OF THIS
 BUILDING IS A CATGORY III AND AN
 IMPORTANCE FACTOR OF 1.15 NOT THE 1.0
 DECLARED.
  
 SHEET S10, "CABLE SIZE AND SPACING PER
 LOCAL BUILDING CODE REQUIREMENTS" IS
 NOT AN ACCEPTABLE SUBSTITUTE FOR
 SPECIFIC DESIGN INFORMATION.SEE SBC
 104.2.
  
 SHEET S1, CITE THE SPECIFIC DESIGN
 STANDARDS AND EDITIONS USED.SEE SBC
 3502
  
 SHOW HOW THE ONE HOUR FIRE RATED
 ASSEMBLY FOR THE ROOF WILL BE
 ACCOMPLISHED.SEE SBC TABLE 600.
  
 AT TIME OF PERMIT APPLICATION PROVIDE
 TEST REPORTS AND/OR PRODUCT NOTICE OF
 ACCEPTANCE REPORTS FOR THE DOORS,
 WINDOWS AND ROOF COVERING.
  
 SPECIFICATIONS 08800 CALL OUT A BROWARD
 COUNTY PRODUCT APPROVAL.THE CITY
 REQUIRES METRO-DADE OR TESTING FROM A
 NATIONAL EVALUATION SERVICE CERTIFYING
 COMPLIANCE WITH SSTD 12-97.