| Date |
Text |
| 2001-08-31 00:00:00 | BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.CALL 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | AS PROVIDED FOR IN SBC 105.3 A RESIDENT |
| | INSPECTOR IS REQUIRED FOR A PROJECT OF |
| | THIS SCOPE.CONTACT DON NEELY AT |
| | 561-659-8096 X 8333 FOR MORE |
| | INFORMATION. |
| | |
| | THIS PROPERTY IS IN A FLOOD ZONE AH BFE |
| | 17.0' NGVD. |
| | |
| | THE FIRE PROTECTION PLANS MUST BE |
| | INCLUDED WITH THE PERMIT PLANS.SEE FS |
| | 553.79 (2). |
| | |
| | THE LS PAGES DO NOT CLEARLY INDICATE THE |
| | LOCATION OF EXISTING OR PROPOSED NEW |
| | SMOKE BARRIER WALLS REQUIRED BY SBC 409. |
| | 1.2.INCLUDE THE EXISTING PORTION OF |
| | THE BUILDING. DEMONSTRATE ALSO THE |
| | REMAINING REQUIREMENTS OF SBC 409. |
| | |
| | THE MAINTENANCE AND STORAGE ROOMS IN THE |
| | VICINITY OF GRID LINES F,3 ARE REQUIRED |
| | TO HAVE FIRE RATED SEPARATION FROM THE |
| | BUILDING BY SBC 409.1.5. |
| | |
| | SHEET S1 CITES ASCE 7-98.THE CITY IS |
| | CURRENTLY USING THE 1997 SBC WHICH |
| | INVOKES ASCE 7-95.FURTHER THE |
| | OCCUPANCY CLASSIFICATION OF THIS |
| | BUILDING IS A CATGORY III AND AN |
| | IMPORTANCE FACTOR OF 1.15 NOT THE 1.0 |
| | DECLARED. |
| | |
| | SHEET S10, "CABLE SIZE AND SPACING PER |
| | LOCAL BUILDING CODE REQUIREMENTS" IS |
| | NOT AN ACCEPTABLE SUBSTITUTE FOR |
| | SPECIFIC DESIGN INFORMATION.SEE SBC |
| | 104.2. |
| | |
| | SHEET S1, CITE THE SPECIFIC DESIGN |
| | STANDARDS AND EDITIONS USED.SEE SBC |
| | 3502 |
| | |
| | SHOW HOW THE ONE HOUR FIRE RATED |
| | ASSEMBLY FOR THE ROOF WILL BE |
| | ACCOMPLISHED.SEE SBC TABLE 600. |
| | |
| | AT TIME OF PERMIT APPLICATION PROVIDE |
| | TEST REPORTS AND/OR PRODUCT NOTICE OF |
| | ACCEPTANCE REPORTS FOR THE DOORS, |
| | WINDOWS AND ROOF COVERING. |
| | |
| | SPECIFICATIONS 08800 CALL OUT A BROWARD |
| | COUNTY PRODUCT APPROVAL.THE CITY |
| | REQUIRES METRO-DADE OR TESTING FROM A |
| | NATIONAL EVALUATION SERVICE CERTIFYING |
| | COMPLIANCE WITH SSTD 12-97. |