Plan Review Notes
Plan Review Notes For Permit 01080252
Permit Number 01080252
Review Stop P
Sequence Number 1
Notes
Date Text
2001-08-23 00:00:00DENIED
  
 REFERENCE SPC-94 AND FACBC-97
  
 1) PAGE MP-1 PLUMBING NOTES. #11 PLEASE
 INSTALL WATER HAMMER ARRESTORS PER MAN-
 UFACTURE'S INSTALLATION INSTRUCTIONS AND
 PDI WH 201.
  
 2) PAGE MP-1 PLUMBING NOTES #12 DIELECT-
 RIC UNIONS NOT APPROVED FOR WATER DIS-
 TRIBUTION PIPE.
  
 3) PAGE MP-1 GENERAL NOTES #1 STANDARD
 PLUMBING CODE 1994 WILL BE USED.
  
 4) PAGE P-2 SANITARY RISER DIAGRAM. W/C
 NOT VENTED PROPERLY. SPC-94 SEC. 914.1
 FIXTURES FROM AN UPPER FLOOR SHALL NOT
 DISCHARGE INTO A BATTERY VENTED BRANCH.
  
 5) PLEASE SUBMIT BACKFLOW INFORMATION
 FOR PLAN REVIEW AND APPROVAL.
  
 6) BACKFLOWS ARE REQUIRED FOR WATER TIED
 INTO INTO CRAC'S. PLEASE SUBMIT MANUFAC-
 TURE'S SPEC. SHEETS FOR THESE UNITS.
 PAGES P-1 AND P-2.
  
 7) PLEASE PROVIED CALCULATIONS FOR MIN-
 IMUM FACILITIES FOR REVIEW. TABLE 407
  
 8) PLEASE PROVIDE CALCULATIONS FOR ROOF
 DRAINAGE. SIZE DOWNSPOUTS AND ALSO SIZE
 SCUPPERS PER SPC-94 SECTION 1108
  
 9) SHOW ACCESSABLE LIFT TO 2ND FLOOR.
 FACBC-97
  
 10) IRRIGATION PERMIT REQUIRED. PLUMBING
 CONTRACTOR TO TIE INTO WATER SERVICE AND
 INSTALL BACKFLOW FOR IRRIGATION CONTRA-
 CTOR.
  
 11) HDCP RESTROOMS 104 & 204. PER FACBC-
 97 SECTION 4.22.2 DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE.
  
 12) DRINKING FOUNTAINS TO COMPLY WITH
 FACBC-97 SECTION 4.15.2
  
 13) SHUTOFF VALVES FOR WATER DISTRIBUT-
 ION TO COMPLY WITH SPC-94 SECTION 610,
 INCLUDING 610.1, 610.4.1 AND 610.4.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377