| 2001-08-23 00:00:00 | DENIED |
| | |
| | REFERENCE SPC-94 AND FACBC-97 |
| | |
| | 1) PAGE MP-1 PLUMBING NOTES. #11 PLEASE |
| | INSTALL WATER HAMMER ARRESTORS PER MAN- |
| | UFACTURE'S INSTALLATION INSTRUCTIONS AND |
| | PDI WH 201. |
| | |
| | 2) PAGE MP-1 PLUMBING NOTES #12 DIELECT- |
| | RIC UNIONS NOT APPROVED FOR WATER DIS- |
| | TRIBUTION PIPE. |
| | |
| | 3) PAGE MP-1 GENERAL NOTES #1 STANDARD |
| | PLUMBING CODE 1994 WILL BE USED. |
| | |
| | 4) PAGE P-2 SANITARY RISER DIAGRAM. W/C |
| | NOT VENTED PROPERLY. SPC-94 SEC. 914.1 |
| | FIXTURES FROM AN UPPER FLOOR SHALL NOT |
| | DISCHARGE INTO A BATTERY VENTED BRANCH. |
| | |
| | 5) PLEASE SUBMIT BACKFLOW INFORMATION |
| | FOR PLAN REVIEW AND APPROVAL. |
| | |
| | 6) BACKFLOWS ARE REQUIRED FOR WATER TIED |
| | INTO INTO CRAC'S. PLEASE SUBMIT MANUFAC- |
| | TURE'S SPEC. SHEETS FOR THESE UNITS. |
| | PAGES P-1 AND P-2. |
| | |
| | 7) PLEASE PROVIED CALCULATIONS FOR MIN- |
| | IMUM FACILITIES FOR REVIEW. TABLE 407 |
| | |
| | 8) PLEASE PROVIDE CALCULATIONS FOR ROOF |
| | DRAINAGE. SIZE DOWNSPOUTS AND ALSO SIZE |
| | SCUPPERS PER SPC-94 SECTION 1108 |
| | |
| | 9) SHOW ACCESSABLE LIFT TO 2ND FLOOR. |
| | FACBC-97 |
| | |
| | 10) IRRIGATION PERMIT REQUIRED. PLUMBING |
| | CONTRACTOR TO TIE INTO WATER SERVICE AND |
| | INSTALL BACKFLOW FOR IRRIGATION CONTRA- |
| | CTOR. |
| | |
| | 11) HDCP RESTROOMS 104 & 204. PER FACBC- |
| | 97 SECTION 4.22.2 DOORS SHALL NOT SWING |
| | INTO THE CLEAR FLOOR SPACE REQUIRED FOR |
| | ANY FIXTURE. |
| | |
| | 12) DRINKING FOUNTAINS TO COMPLY WITH |
| | FACBC-97 SECTION 4.15.2 |
| | |
| | 13) SHUTOFF VALVES FOR WATER DISTRIBUT- |
| | ION TO COMPLY WITH SPC-94 SECTION 610, |
| | INCLUDING 610.1, 610.4.1 AND 610.4.2 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT. 8377 |