Plan Review Notes
Plan Review Notes For Permit 01080252
Permit Number 01080252
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-07 00:00:001) PLEASE INDICATE ANTICIPATED OCCUPANT
 LOADS FOR THE BUILDING.
 2) PLEASE INDICATE FIRE AND PARAMEDICAL
 ACCESS TO THE BUILDING. GATES SHALL
 PROVIDE AT LEAST 20 FEET IN CLEAR
 WIDTH.
 3) NEW FIRE HYDRANT TO COMPLY WITH
 UTILITY AND FIRE RESCUE STANDARDS.
 4) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE EMERGENCY GENERATOR AND ANY
 FUEL SUPPLIES ASSOCIATED WITH IT.
 5) BUILDING ADDRESS REQUIRED PER CITY
 CODE REQUIREMENTS.
 6) BUILDING APPEARS TO BE WINDOWLESS. IF
 WINDOWS ARE NOT PROVIDED FOR RESCUE OR
 VENTILATION PURPOSES, THE BUILDING WILL
 HAVE TO BE FIRE SPRINKLER PROTECTED.
 PLEASE SEE NFPA 101, THE LIFE SAFETY
 CODE, 1985 EDTION, SECTION 30-1.3.5.
  