| 2001-08-21 00:00:00 | **************** UNSAT ************** | | | | | | 1) NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) PER 215-3 AND | | | 230-42. PLEASE SHOW LOAD CALCUALTIONS | | | COMPLETED, INLCUDING FINAL AMPERAGES. | | | | | | 2)NOTE: PLEASE PLACE NOTE ON PLANS FOR | | | ALL EQUIPMENT DISCONNECTING MEANS TO | | | BE LABELED.PLEASE PLACE ON RISER DIAGRAM | | | | | | 3)NOTE: PLEASE CLARIFY MANUAL MEANS OF | | | DISCONNECT PER 230-76 FOR MAINS. | | | PLEASE NOTE 230-79 | | | | | | 4)NOTE: PLEASE NOTE THAT BUILDING FOOTER | | | STEEL TO BE PART OF THE GROUNDING | | | ELECTRODE SYSTEM. PER 250-50. | | | | | | 5)NOTE: PLEASE NOTE THAT COLOR CODING | | | IS NOTED ON E1-1. PLEASE NOTE LOCAL | | | AMENDMENTS FOR 277/480. BR/PURP/YELLOW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|