Plan Review Notes
Plan Review Notes For Permit 01080252
Permit Number 01080252
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-21 00:00:00**************** UNSAT **************
  
 1) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC) PER 215-3 AND
 230-42. PLEASE SHOW LOAD CALCUALTIONS
 COMPLETED, INLCUDING FINAL AMPERAGES.
  
 2)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 ALL EQUIPMENT DISCONNECTING MEANS TO
 BE LABELED.PLEASE PLACE ON RISER DIAGRAM
  
 3)NOTE: PLEASE CLARIFY MANUAL MEANS OF
 DISCONNECT PER 230-76 FOR MAINS.
 PLEASE NOTE 230-79
  
 4)NOTE: PLEASE NOTE THAT BUILDING FOOTER
 STEEL TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM. PER 250-50.
  
 5)NOTE: PLEASE NOTE THAT COLOR CODING
 IS NOTED ON E1-1. PLEASE NOTE LOCAL
 AMENDMENTS FOR 277/480. BR/PURP/YELLOW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372