| Plan Review Notes For Permit 01080230 |
| Permit Number |
01080230 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-04 00:00:00 | DENIED | | | 1. PROVIDE DUCT AND DROP SIZES AND CFM | | | INFORMATION FOR ADDITIONAL AIR | | | CONDITIONING. PROVIDE LOCATION OF DROPS | | | AND THE TIE IN TO EXISTING SYSTEM. | | | 2. PROVIDE DRYEREXHAUST DUCT | | | INFORMATIONINCLUDING TERMINATION | | | LOCATION. | | | 3. PROVIDE INFORMATION ON BATHROOM | | | EXHAUST FAN DUCT INCLUDING TERMINATION | | | LOCATION. | | | 1997 MODEL COUNTYWIDE AMENDMENTS AS | | | AMENDED TO THE STANDARD CODES 104.2 | | | REQUIRES PLANS TO BE OF SUFFICIENT | | | CLARITY AND DETAILS TO INDICATE THE | | | NATURE OF THE WORK. |
|