Plan Review Notes
Plan Review Notes For Permit 01080159
Permit Number 01080159
Review Stop E
Sequence Number 4
Notes
Date Text
2002-02-11 00:00:00**************** UNSAT ***************
  
 PLEASE NOTE AS ASKED FOR ON PREVIOUS
 REVIEWS. IF THEREARE ANY QUESTIONS,
 PLEASE CALL.
  
 1)NOTE: PLEASE NOTE ANOTHER NEW RISER
 DIAGRAM WAS SUBMITTED FOR REVIEW.
 NOW PLANS ARE SHOWING FOUR MAIN MEANS
 OF DISCONNECT??
 PLEASE CLARIFY TWO MAIN DISCONNECTS AND
 THEN TWO MAIN BREAKERS? AND THEN TO THE
 TWO PANELS.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 AIC RATING SHOWN FOR BRKRS ONLY?
 NOTHING SUBMITTED FOR MAINS.
  
 3)NOTE: PLEASE NOTE NO EQUIPMENT
 GROUNDING SHOWN BETWEEN MAINS AND
 PANELS 250-122.
  
 PLEASE NOTE THAT ELECTRICAL RISER IS
 SHOWING 2/0 WIRE FROM GUTTER TO 100A
 PANELS. PLEASE NOTE THAT THIS IS OVER-
 SIZED, WHICH IS OK, BUT IF 2/0 IS SHOWN
 ON PLAN THEN THATS WHAT WILL BE REQ`D
 TO BE INSTALLED. PLEASE NOTE THAT PER
 310-16, #3 IS OK FOR 100AMPS. PLEASE
 NOTE THAT SOMETIMES A 2/0 WILL NOT FIT
 IN 100A BRKRS/ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372