| 2002-02-11 00:00:00 | **************** UNSAT *************** |
| | |
| | PLEASE NOTE AS ASKED FOR ON PREVIOUS |
| | REVIEWS. IF THEREARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | 1)NOTE: PLEASE NOTE ANOTHER NEW RISER |
| | DIAGRAM WAS SUBMITTED FOR REVIEW. |
| | NOW PLANS ARE SHOWING FOUR MAIN MEANS |
| | OF DISCONNECT?? |
| | PLEASE CLARIFY TWO MAIN DISCONNECTS AND |
| | THEN TWO MAIN BREAKERS? AND THEN TO THE |
| | TWO PANELS. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | AIC RATING SHOWN FOR BRKRS ONLY? |
| | NOTHING SUBMITTED FOR MAINS. |
| | |
| | 3)NOTE: PLEASE NOTE NO EQUIPMENT |
| | GROUNDING SHOWN BETWEEN MAINS AND |
| | PANELS 250-122. |
| | |
| | PLEASE NOTE THAT ELECTRICAL RISER IS |
| | SHOWING 2/0 WIRE FROM GUTTER TO 100A |
| | PANELS. PLEASE NOTE THAT THIS IS OVER- |
| | SIZED, WHICH IS OK, BUT IF 2/0 IS SHOWN |
| | ON PLAN THEN THATS WHAT WILL BE REQ`D |
| | TO BE INSTALLED. PLEASE NOTE THAT PER |
| | 310-16, #3 IS OK FOR 100AMPS. PLEASE |
| | NOTE THAT SOMETIMES A 2/0 WILL NOT FIT |
| | IN 100A BRKRS/ETC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMAITON FOR |
| | REVIEW. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-659-8096 EXT 8372 |