| 2001-12-24 00:00:00 | ****************** UNSAT *********** |
| | |
| | PLEASE NOTE NOT ALL NOTES FROM FIRST |
| | REVIEW WERE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE NOTE THAT NOW A COMPLETE- |
| | -LY NEW RSIER DIAGRAM IS BEING SUBMITTED |
| | AND THERE ARE NEW COMMENTS FOR THAT. |
| | |
| | A) PLEASE NOTE THAT NO AIC RATINGS WERE |
| | SUBMITTED FOR ANY OF THE NEWM EQUIPMENT |
| | SHOWN. 110-9 / 215-5 |
| | |
| | B)NOTE: PLEASE NOTE THAT THERE IS NO |
| | GROUNDING SYSTEM SHOWN AT DETACHED BLDG |
| | PER 250-32. |
| | |
| | C) PLEASE NOTE THAT NO EQUIPMENT GROUND- |
| | -ING CONDUCTORS ARE SHOWN FROM MAIN |
| | PANEL TO EITHER, HOUSE PANEL OR COTTAGE |
| | 250-122. |
| | |
| | D) PLEASE NOTE THEREIS NO INDICATION |
| | ON COTTAGE PANEL IF THERE IS A MAIN |
| | BRKR? PLEASE SHOW 225-31 |
| | |
| | E) PLEASE NOTE THAT THERE IS NO PANEL |
| | SCHEDULE FOR MAIN PANEL, PLEASE SHOW |
| | WITH THE SIZE OF OCP GOING TO EACH PANEL |
| | PLEASE CLARIFY, IF THERE IS 100 OCP, |
| | PLEASE NOTE 2/0 CONDUCTORS GOING TO A |
| | 100 BRKR. PLEASENOTE IF THEY'LL FIT? |
| | PLEASE NOTE PER 310-16 #3 IS ALL THAT |
| | IS REQ`D FOR 100A`S. |
| | |
| | F) PLEASE NOTE THAT NO MIN LAUNDRY |
| | CIRCUIT IS SHOWN. 210-52 F. |
| | |
| | 2)NOTE: PLEASE NOTE THAT OUTLET SPACING |
| | NEEDS TO MEET 210-52.CHIEF BLDG INSPECT- |
| | -OR HAS NOTED HOUSE IS BEING COMPLETETLY |
| | RE-DONE. |
| | |
| | 3) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | |
| | 4)NOTE: PLEASE NOTE THAT THERE IS A NEW |
| | SHEET 1 ATTACHED AND SHOWS LOCATION OF |
| | METER AT DETACHED BLDG? PLEASE NOTE THAT |
| | LOCATION OF SERVICE NEEDS TO BE CLARIFIE |
| | -D. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |