Plan Review Notes
Plan Review Notes For Permit 01080159
Permit Number 01080159
Review Stop E
Sequence Number 1
Notes
Date Text
2001-09-27 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT REAR APT/
 IS NOT ALLOWED BY ZONING.
  
 2)NOTE: PLEASE NOTE THAT IF ALLOWED TO
 BE GARAGE/APT THE SERVICES WOULD STILL
 HAVE TO BE GROUPED ON ONE BLDG WITH
 MAINS GROUPED AND THEN SUB FEEDING
 DETACHED BLDG, WHEATHER SERVICE IS ON
 MAIN HOUSE OR APT.230-2/230-72
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) NOTE: PLEASE SHOW ALL OUTLETS
 SERVINGKITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
  
 5)NOTE: PLEASE NOTE THAT MAIN HOUSE
 KITCHEN COUNTERSPACE IS NOT
 SHOWN,PLEASESHOW AND SHOW OUTLET
 SPACING TO MEET 210-52 C
  
 6) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 7)NOTE: PLEASE NOTE THAT OVERHEAD
 SERVICE IS SHOWN WITH A 10' MIN CLEARENC
 E FROM GROUND TO THE TOP OF THE WEATHER
 HEAD. PLEASE NOTE THAT THE CLEARENCE
 IS FROM THE GROUND TO THE BOTTOM OF THE
 DRIP LOOP. 230-24
  
 8)NOTE: PLEASE SHOW LOAD CALCULATIONS TO
 MEET ART 220.
  
 9)NOTE: PLEASE INDICATE MCB FOR PANEL(S)
 OR MAIN DISC WHEN GOING WITH SERVICE ON
 ONE BLDG.,
  
 10)NOTE: PLEASE NOTE THAT ALL GEN LT
 PER PANEL SCHEDULE SHOW #14, 15A, PLEASE
 NOTE THAT DING ROOMTO BE #12,20A PER
 210-52
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372