| 2001-09-27 00:00:00 | *************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT REAR APT/ |
| | IS NOT ALLOWED BY ZONING. |
| | |
| | 2)NOTE: PLEASE NOTE THAT IF ALLOWED TO |
| | BE GARAGE/APT THE SERVICES WOULD STILL |
| | HAVE TO BE GROUPED ON ONE BLDG WITH |
| | MAINS GROUPED AND THEN SUB FEEDING |
| | DETACHED BLDG, WHEATHER SERVICE IS ON |
| | MAIN HOUSE OR APT.230-2/230-72 |
| | |
| | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 4) NOTE: PLEASE SHOW ALL OUTLETS |
| | SERVINGKITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECT--ED PER 210-8-A-6. |
| | |
| | 5)NOTE: PLEASE NOTE THAT MAIN HOUSE |
| | KITCHEN COUNTERSPACE IS NOT |
| | SHOWN,PLEASESHOW AND SHOW OUTLET |
| | SPACING TO MEET 210-52 C |
| | |
| | 6) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 7)NOTE: PLEASE NOTE THAT OVERHEAD |
| | SERVICE IS SHOWN WITH A 10' MIN CLEARENC |
| | E FROM GROUND TO THE TOP OF THE WEATHER |
| | HEAD. PLEASE NOTE THAT THE CLEARENCE |
| | IS FROM THE GROUND TO THE BOTTOM OF THE |
| | DRIP LOOP. 230-24 |
| | |
| | 8)NOTE: PLEASE SHOW LOAD CALCULATIONS TO |
| | MEET ART 220. |
| | |
| | 9)NOTE: PLEASE INDICATE MCB FOR PANEL(S) |
| | OR MAIN DISC WHEN GOING WITH SERVICE ON |
| | ONE BLDG., |
| | |
| | 10)NOTE: PLEASE NOTE THAT ALL GEN LT |
| | PER PANEL SCHEDULE SHOW #14, 15A, PLEASE |
| | NOTE THAT DING ROOMTO BE #12,20A PER |
| | 210-52 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |