| Plan Review Notes For Permit 01080143 |
| Permit Number |
01080143 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2002-06-26 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE GROUNDING ELECTRODE | | | SYSTEM HAS BEEN REVISED AND IS MISSING | | | BLDG/FOOTER STEEL. PER 250-50. PLEASE | | | NOTE THIS WAS ON FIRST SET OF PLANS AND | | | WAS AVAILABLE AT TIME OF CONSTRUCTION!! | | | | | | 2)NOTE: PLEASE ALSO NOTE THAT SHEET E-6 | | | IS NOT SIGNED,DATED OR SEALED ON EITHER | | | SET. REQ`D PER FS/FAC 61G15-23.002, 471. | | | .025. | | | | | | PLEASE SUBMIT THE ABOVE REVISED PLANS | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|