Plan Review Notes
Plan Review Notes For Permit 01080143
Permit Number 01080143
Review Stop E
Sequence Number 4
Notes
Date Text
2002-06-26 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE GROUNDING ELECTRODE
 SYSTEM HAS BEEN REVISED AND IS MISSING
 BLDG/FOOTER STEEL. PER 250-50. PLEASE
 NOTE THIS WAS ON FIRST SET OF PLANS AND
 WAS AVAILABLE AT TIME OF CONSTRUCTION!!
  
 2)NOTE: PLEASE ALSO NOTE THAT SHEET E-6
 IS NOT SIGNED,DATED OR SEALED ON EITHER
 SET. REQ`D PER FS/FAC 61G15-23.002, 471.
 .025.
  
 PLEASE SUBMIT THE ABOVE REVISED PLANS
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372