2001-10-21 00:00:00PLUMBING PLAN REVIEW DENIED, PLEASE
 ADDRESS PREVIOUS NOTES DATED 08-21-01.
 (1) DEPT OF HOTEL BUSINESS REGULATION
 PLAN REVIEW, REQUIRED BEFORE A PLUMBING
 PLAN REVIEW CAN BE COMPLETED.SEC 101.4.7
 (2) SHT P-3,4 GREASE TRAP SIZE, W PALM
 BEACH ENVIROMENTAL COMPLIANCE, CONTACT
 RODNEY COMPO 561-837-4074.
 (8) SHT P2 CONSTRUCTION NOTE #2, LOCAL
 ORDINANCE FOR BACKFLOW PREVTERS #2853-95
 TYPE AND LOCATION, CONTACT 561-659-8000
 EXT 2008. W. PALM BCH WATER DEPT.
 (13) SHT AI, MENS RM #107 URINAL SHALL
 BE SCREENED FOR PRIVACY,SEC 404.3ALSO
 CLEAR FLOOR SPACE, FACBC-97 SEC 4.18.3
 END OF COMMENTSPAUL SCHMITZ