2001-10-15 00:00:00FAILED :
 1. PLEASE CALL-OUT THE GREASE/WATER
 SEPARATOR AND REFER TO PLUMBING PLAN FOR
 DETAILS, PLUMBING PLAN SHOWS TWO.
 PLEASE CALL RODNEY COMPO 873-4051 EXT.
 4074 FOR QUESTIONS, INSTALLATION AND
 INSPECTIONS.
 2. ANY NEW CONNECTIONS TO CITY SERVICES
 WOULD REQUIRE A SEPARATE PERMIT FROM
 PUBLIC UTILITIES AND ANY WORK WITHIN
 PUBLIC R.O.W ALSO, REQUIRES A PERMIT
 FROM CITY ENGINEER, 659-8040.
 3. SHEET 3 OF 4 " WATER METER DETAILS"
 REFERS TO METER AND METER BOX BY CITY,
 PLEASE BE ADVISE THAT CITY PROVIDES
 METERS ONLY.NOTE 1 REFER TO "K" COPPER
 TUBING OR POLYETHYLENE TUBING, PLRASE
 USE TYPE "K" COPPER TUBING.
 3. PLEASE PROVIDE STOP BARS AND STOP
 SIGNS AT ALL DRIVEWAYS.
 4. PLEASE PROVIDE PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR ENTIRE SITE,
 SIGNED AND SEALED.
 5. WE RECOMMEND A SEPARATE PERMIT
 APPLICATION FOR SITE AND UNDERGROUND
 UTILITIES WORK.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096