| 2001-10-22 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01080143 |
| | 2031 PALM BEACH LAKES |
| | KRISP KREME |
| | "2ND PLAN REVIEW" |
| | CONT PER: RICHARD SIDES |
| | TEL: (336) 725-2981 |
| | FAX: (336) 733-3798 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS/ STANDARD BUILDING CODE |
| | |
| | **** PLANS ARE BEING REVIEWED UNDER THE |
| | 1997 STANDARD BUILDING CODE, IF APPLICA- |
| | TION FOR PERMIT HAS NOT BEEN MADE BEFORE |
| | DECEMBER 31,2001 THE PLANS WILL BE |
| | REVIEWED UNDER THE 2001 FLORIDA BUILDING |
| | CODE.**** |
| | |
| | 1)- THIS BUILDING WILL BE LOCATED IN THE |
| | FIRE FISTRICT, TYPE VI BUILDINGS ARE NOT |
| | ALLOWED IN A FIRE DISRICT. |
| | SBC 607 TYPE V BUILDING: EXTERIOR |
| | WALLS BEARING & NONBEARING ARE OF NON- |
| | COMBUSTIBLE MATERIALS. |
| | BY DEFINITION EXTERIOR WALLS,A WALL, |
| | BEARING OR NON BEARING WHICH IS USED AS |
| | AN ENCLOSING WALL FOR A BUILDING, OTHER |
| | THAN A PARTY WALL OR FIRE WALL. |
| | SHEET A-6 DETAIL#3 INDICATES COMBUST |
| | IBLE ELEMENTS WITHIN THE EXTERIOR WALL, |
| | (OSB BOARD, 2X6 FURRING & EFIS SYSTEM). |
| | EFIS SYSTEMS PROVIDE PRODUCT TESTING |
| | REPORT MEETING THE REQUIREMENTS OF |
| | NONCOMBUSTIBLE BUILDING MATERIAL,AS SET |
| | FORTH IN ASTM E 136. |
| | |
| | 2)- SBC 1606.2.6.2 A SKETCH SHOWING THE |
| | VARIOUS WIND PRESSURE ZONES FOR WALLS, |
| | ROOF AND END ZONES. |
| | |
| | 3)- 1606.4.1/ 1707.4.1* SBC. THE CITY |
| | CODE INTERPRETATION FOR LARGE MISSLE |
| | HURRICANE RESISTANT GLAZING OR STORM |
| | SHUTTERS. SEE CITY INTERPRETATION, |
| | FOR STORM SHUTTERS A INSTALATION SCHED- |
| | ULE & KEY PLAN WILL BE REQUIRED. |
| | THE CITY ACCEPTS PRODUCT TESTING |
| | REPORTS FROM S.B.C.C.I. OR DADE COUNTY |
| | PRODUCT APPROVAL REPORTS.(2 COPIES) |
| | |
| | 4)- ROOF ASSEMBLIES SBC 1503.3.2. |
| | SHOW PRODUCT ACCEPTANCE FOR 110 MPH WIND |
| | ZONE. SBCCI OR DADE COUNTY REPORT, |
| | 2 COPIES. |
| | |
| | 5)- SBC: F102.2.4. ROOF COVERINGS IN A |
| | FIRE DISTRICT SHALL CONFORM TO THE |
| | REQUIREMENTS OF A CLASS A OR B ROOF. |
| | PROVIDE MANUFACTURES SPECIFICATION. |
| | |
| | 6)- DOOR 115A SWING DOOR & DOOR 115 |
| | OVERHEAD ARE MISSING PRODUCT APPROVAL |
| | REPORTS.SBC 1606.2.6.2. |
| | |
| | 7)- PLANS ARE TO HAVE COUNTY IMPACT FEE |
| | STAMP BEFORE THE ISSUANCE OF PERMIT. |
| | CONTTRACTOR RESPONSIBLIITY. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096X8412 |