Plan Review Notes
Plan Review Notes For Permit 01080143
Permit Number 01080143
Review Stop P
Sequence Number 1
Notes
Date Text
2001-08-21 00:00:00DENIED
  
 REFERENCES- SPC-94 - SGC-97 - FACBC-97
  
 1) PLANS SHALL BE ROUTED TO DEPT. OF
 BUSINESS REGULATION FOR REVIEW AND APP-
 ROVAL. COUNTY WIDE AMENDMENTS TO SPC
 SEC. 101.4.7.
  
 2) GREASE TRAPS TO BE LOCATED & SIZED BY
 UTILITY DEPT. PLEASE CONTACT RODNEY
 COMPO (561) 837-4074. SEPARATE PERMIT
 FOR GREASE TRAP, PROVIDER TO PULL PERMIT
 APPROVED GREASE TRAP DETAIL (SEE ATTACH-
 ED).
  
 3) PAGE P-1 GENERAL NOTE #9, WATER HAM-
 MER ARRESTORS TO BE LOCATED & SIZED PER
 MANUFACTURES INSTALLATION INSTRUCTIONS.
  
 4) SEARATE PERMIT FOR GAS. SEE ATTACHED
 SHEET FOR GAS PERMIT REQUIREMENTS. ADD-
 RESS ALL SECTIONS IN RED FOR PLAN REVIEW
  
 5) PAGE P-1, CONST. NOTES #5. RESTROOM
 SOIL PIPING TO TIE INTO SANITARY DOWN-
 STREAM OF GREASE TRAP.
  
 6) PAGE P-1, CONST. NOTES #'S 2,3 & 7,
 CONDENSATE FROM A/C NOT ALLOWED TO TIE
 INTO SANITARY. MUST GO TO STORM OR DRY-
 WELL.
  
 7) PAGE P-1, CONST NOTES #'S 4,13 & 14.
 HUB DRAINS NOT ALLOWED. FLOOR SINK REQ-
 UIRED FOR ALL INDIRECT WASTE.
  
 8) PAGE P-2, CONST. NOTES #2. BACKFLOW
 TO BE INSTALLED HORIZONTALLY, MAXIMUM OF
 4'0" OFF FLOOR FOR SERVICING. DRAIN TO
 FLOOR SINK.
  
 8) PAGE P-2, CONST. NOTES #3. WATER
 FILTRATION SYSTEM SHALL BE NSF APPROVED
 PER SPC-94 615.1 & 615.2. SUBMIT MANU-
 FACTURE SPEC./INFORMATION SHEETS.
  
 9) PAGE PME1, GENERAL NOTES #8. ROOF
 DRAINS TO BE INSTALLED BY PLUMBING CON-
 TRACTOR.
  
 10) PAGE PME1, GENERAL NOTES #12. CONDEN
 SATE TO BE RUN TO STORM OR DRYWELL.
  
 11) PAGE SP4, NOTE 3.02 L. AIR CHAMBERS
 TO COMPLY WITH SPC-94 607.8.2 & 607.8.3,
 ACCESSABLE AND RECHARGABLE. MUST MEET
 PDI WH 201 REQUIREMENTS FOR RECHARGING.
  
 12) PAGE A1, EMPLOYEE TOILET RM 119.
 DOOR SHALL NOT OPEN INTO CLEAR FLOOR
 SPACE OR TURNING RADIUS. FACBC-97 4.22.2
  
 13) PAGE A1, RM 107 MEN'S RESTROOM. PER
 SPC-94 TABLE 407 - FOOTNOTE #3, A URNAL
 IS REQUIRED.
  
 14) PLEASE SUBMIT INFORMATION/DETAILS
 FOR ROOF DRAINAGE. COMPLY WITH SPC-94
 SEC. 1108.1, 1108.2. ALSO SEE FIGURE
 1108.4. INCLUDE INFO FOR SECONDARY DRAIN
 AGE PER SPC SEC. 1109.
  
 15) PAGE P2, WATER SUPPLY SYSTEM IS
 LACKING CONTROL VALVES. COMPLY WITH SPC
 SEC. 610.4.1
  
 16) PAGE P2, WATER SUPPLY CONTROL VALVES
 REQUIRED ON BRANCH LINES PER SPC SEC
 610.4.2.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377