| 2001-08-21 00:00:00 | DENIED |
| | |
| | REFERENCES- SPC-94 - SGC-97 - FACBC-97 |
| | |
| | 1) PLANS SHALL BE ROUTED TO DEPT. OF |
| | BUSINESS REGULATION FOR REVIEW AND APP- |
| | ROVAL. COUNTY WIDE AMENDMENTS TO SPC |
| | SEC. 101.4.7. |
| | |
| | 2) GREASE TRAPS TO BE LOCATED & SIZED BY |
| | UTILITY DEPT. PLEASE CONTACT RODNEY |
| | COMPO (561) 837-4074. SEPARATE PERMIT |
| | FOR GREASE TRAP, PROVIDER TO PULL PERMIT |
| | APPROVED GREASE TRAP DETAIL (SEE ATTACH- |
| | ED). |
| | |
| | 3) PAGE P-1 GENERAL NOTE #9, WATER HAM- |
| | MER ARRESTORS TO BE LOCATED & SIZED PER |
| | MANUFACTURES INSTALLATION INSTRUCTIONS. |
| | |
| | 4) SEARATE PERMIT FOR GAS. SEE ATTACHED |
| | SHEET FOR GAS PERMIT REQUIREMENTS. ADD- |
| | RESS ALL SECTIONS IN RED FOR PLAN REVIEW |
| | |
| | 5) PAGE P-1, CONST. NOTES #5. RESTROOM |
| | SOIL PIPING TO TIE INTO SANITARY DOWN- |
| | STREAM OF GREASE TRAP. |
| | |
| | 6) PAGE P-1, CONST. NOTES #'S 2,3 & 7, |
| | CONDENSATE FROM A/C NOT ALLOWED TO TIE |
| | INTO SANITARY. MUST GO TO STORM OR DRY- |
| | WELL. |
| | |
| | 7) PAGE P-1, CONST NOTES #'S 4,13 & 14. |
| | HUB DRAINS NOT ALLOWED. FLOOR SINK REQ- |
| | UIRED FOR ALL INDIRECT WASTE. |
| | |
| | 8) PAGE P-2, CONST. NOTES #2. BACKFLOW |
| | TO BE INSTALLED HORIZONTALLY, MAXIMUM OF |
| | 4'0" OFF FLOOR FOR SERVICING. DRAIN TO |
| | FLOOR SINK. |
| | |
| | 8) PAGE P-2, CONST. NOTES #3. WATER |
| | FILTRATION SYSTEM SHALL BE NSF APPROVED |
| | PER SPC-94 615.1 & 615.2. SUBMIT MANU- |
| | FACTURE SPEC./INFORMATION SHEETS. |
| | |
| | 9) PAGE PME1, GENERAL NOTES #8. ROOF |
| | DRAINS TO BE INSTALLED BY PLUMBING CON- |
| | TRACTOR. |
| | |
| | 10) PAGE PME1, GENERAL NOTES #12. CONDEN |
| | SATE TO BE RUN TO STORM OR DRYWELL. |
| | |
| | 11) PAGE SP4, NOTE 3.02 L. AIR CHAMBERS |
| | TO COMPLY WITH SPC-94 607.8.2 & 607.8.3, |
| | ACCESSABLE AND RECHARGABLE. MUST MEET |
| | PDI WH 201 REQUIREMENTS FOR RECHARGING. |
| | |
| | 12) PAGE A1, EMPLOYEE TOILET RM 119. |
| | DOOR SHALL NOT OPEN INTO CLEAR FLOOR |
| | SPACE OR TURNING RADIUS. FACBC-97 4.22.2 |
| | |
| | 13) PAGE A1, RM 107 MEN'S RESTROOM. PER |
| | SPC-94 TABLE 407 - FOOTNOTE #3, A URNAL |
| | IS REQUIRED. |
| | |
| | 14) PLEASE SUBMIT INFORMATION/DETAILS |
| | FOR ROOF DRAINAGE. COMPLY WITH SPC-94 |
| | SEC. 1108.1, 1108.2. ALSO SEE FIGURE |
| | 1108.4. INCLUDE INFO FOR SECONDARY DRAIN |
| | AGE PER SPC SEC. 1109. |
| | |
| | 15) PAGE P2, WATER SUPPLY SYSTEM IS |
| | LACKING CONTROL VALVES. COMPLY WITH SPC |
| | SEC. 610.4.1 |
| | |
| | 16) PAGE P2, WATER SUPPLY CONTROL VALVES |
| | REQUIRED ON BRANCH LINES PER SPC SEC |
| | 610.4.2. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT. 8377 |