| Plan Review Notes For Permit 01080143 |
| Permit Number |
01080143 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-07 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY | | | CODE 3343-00. | | | 2) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE HOOD, DUCT, AND EXTINGUISHING | | | SYSTEM PLANNED FOR USE. | | | 3) ELEVATION DRAWINGS DISPLAYS FIRE | | | ALARM EQUIPMENT BUT THE BUILDING CODE | | | SUMMARY INDICATES THAT NO FIRE ALARM | | | SYSTEM WILL BE PRESENT. | | | 4) ANOTHER EMERGENCY LIGHT FIXTURE | | | APPEARS TO BE NEEDED IN THE INGREDIENT | | | ROOM. | | | 5) PRODUCT APPROVALS ARE REQUIRED TO | | | BE SUBMITTED FOR THE ONE HOUR FIRE | | | SHIELDING WHEN THE HOOD PERMIT IS | | | SUBMITTED. | | | 6) DUCT SMOKE DETECTORS ARE REQUIRED | | | IN AIR HANDLING EQUIPMENT OVER 2000 CFM. | | | 7) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 8) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | 9) NO INTERIOR FINISH INFORMATION | | | PROVIDED FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|