Plan Review Notes
Plan Review Notes For Permit 01080143
Permit Number 01080143
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-07 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE HOOD, DUCT, AND EXTINGUISHING
 SYSTEM PLANNED FOR USE.
 3) ELEVATION DRAWINGS DISPLAYS FIRE
 ALARM EQUIPMENT BUT THE BUILDING CODE
 SUMMARY INDICATES THAT NO FIRE ALARM
 SYSTEM WILL BE PRESENT.
 4) ANOTHER EMERGENCY LIGHT FIXTURE
 APPEARS TO BE NEEDED IN THE INGREDIENT
 ROOM.
 5) PRODUCT APPROVALS ARE REQUIRED TO
 BE SUBMITTED FOR THE ONE HOUR FIRE
 SHIELDING WHEN THE HOOD PERMIT IS
 SUBMITTED.
 6) DUCT SMOKE DETECTORS ARE REQUIRED
 IN AIR HANDLING EQUIPMENT OVER 2000 CFM.
 7) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 8) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 9) NO INTERIOR FINISH INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910