Plan Review Notes
Plan Review Notes For Permit 01080143
Permit Number 01080143
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-22 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED FOR REVIEW.
 PLEASE SUBMIT. 215-5
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
  
 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
  
 5)NOTE: PLEASE NOTE THAT OUTLET SPACING
 IS TO MEET LOCAL CODE 210-50. EVERY 20`
 OF WALL SPACE SEATING/LOBBY, HALL,
 BREAK ROOM.
  
 6)NOTE: PLEASE NOTE OUTLET SPACING FOR
 SHOW WINDOWS PER 210-62
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372