| Plan Review Notes For Permit 01080143 |
| Permit Number |
01080143 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-22 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE NOTE THAT NO LOAD | | | CALCULATIONS WERE SUBMITTED FOR REVIEW. | | | PLEASE SUBMIT. 215-5 | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) | | | | | | 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BUILDING STEEL AND COLD WATER | | | PER 250-50. | | | | | | 5)NOTE: PLEASE NOTE THAT OUTLET SPACING | | | IS TO MEET LOCAL CODE 210-50. EVERY 20` | | | OF WALL SPACE SEATING/LOBBY, HALL, | | | BREAK ROOM. | | | | | | 6)NOTE: PLEASE NOTE OUTLET SPACING FOR | | | SHOW WINDOWS PER 210-62 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|