| 2001-09-05 00:00:00 | THIS BUILDING WILL BE LOCATED IN THE |
| | DESIGNATED FIRE DISTRICT AND TYPE VI |
| | CONSTRUCTION (WOOD FRAME) IS NOT |
| | ALLOWED.SEE SBC F102.1. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, THE PERMIT PLANS STAMPED |
| | BY THAT OFFICE AND A COPY OF THE |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025 FOR |
| | MORE INFORMATION. |
| | |
| | A SITE PLAN AND SURVEY WERE NOT INCLUDED |
| | SO A COMPLETE PLAN REVIEW WAS NOT |
| | POSSIBLE. |
| | |
| | SHEET S2CALLS OUT A WIND UPLIFT THE |
| | ROOF TRUSSES OF 90 MPH.THE DESIGNER |
| | OF RECORD SHOULD INDICATE THE LOCATION, |
| | DIRECTION, MAGNITUDE AND NATURE OF THE |
| | FORCES TO BE RESISTED WHEN DELEGATING |
| | DESIGN TO A SPECIALTY ENGINEER. INCLUDED |
| | COMPLETE STRUCTURAL CALCULATIONS WITH |
| | THE PERMIT APPLICATION.SEE SBC 104.2. |
| | |
| | |
| | THE CITY CURRENTLY INVOKES THE 1997 |
| | STANDARD BUILDING CODE WHICH IS NOT |
| | INDICATED ON SHEET T1.ALSO INDICATE |
| | THE EDITIONS OF THE DESIGN STANDARDS |
| | USED.SEE SBC 3502. |
| | |
| | SHOW HOW THE GLAZED PORTIONS OF THE |
| | BUILDING WILL RESIST HURRICANE MISSILE |
| | IMPACT.SEE THE ATTACHED "CODE |
| | INTERPRETATION" |
| | |
| | AT TIME OF PERMIT APPLICATION PROVIDE |
| | COPIES OF TEST REPORTS FROM A |
| | RECOGNIZED EVALUATION SERVICE OR |
| | METRO-DADE NOTICE OF ACCEPTANCE REPORTS |
| | FOR THE DOORS, WINDOWS AND ROOF |
| | COVERING. |
| | |
| | AT TIME OF PERMIT APPLICATION LINCLUDE A |
| | SKETCH OF THE BUILDING SHOWING THE WIND |
| | PRESSURE ZONES.SEE SBC 1606.2.6.2 |
| | ANDSBC 1606.3. |
| | |
| | PROVIDE A SEATING PLAN, SEE SBC |
| | 1003.1.2. |