Plan Review Notes
Plan Review Notes For Permit 01080132
Permit Number 01080132
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-28 00:00:001) NO DETAILS PROVIDED FOR ANY FIRE
 SUPPRESSION SYSTEM PLANNED FOR BOOTH.
 A FIRE SUPPRESSION SYSTEM IS REQUIRED.
 SEPARATE PLANS AND PERMITS REQUIRED.
 2) HOW IS SPRAY BOOTH GROUNDED.
 3) MORE DETAILS NEEDED ON FILTER PLANNED
 FOR USE. FILTERS ARE REQUIRED TO COMPLY
 WITH CERTAIN CRITERIA.
 4) NO DETAILS PROVIDED ON FIREWRAP
 MATERIAL NOTED ON DUCT DIAGRAM.
 5) PLEASE CLEARLY NOTE ON THE PLANS
 THAT THE EXHAUST DUCT EXTENDS AT LEAST
 SIX FEET ABOVE THE ROOF.
 6) CLEARLY NOTE THE REQUIRED 3 FEET
 LOCATED FOR AROUND THE SPRAY BOOTH.
 7) WHAT WILL THE SPRAY BOOTH BE USED
 FOR.
 8) ARE THERE ANY FLAMMABLE LIQUID
 CABINETS PLANNED FOR THE AREA.
  