| 2001-08-28 00:00:00 | 1) NO DETAILS PROVIDED FOR ANY FIRE | | | SUPPRESSION SYSTEM PLANNED FOR BOOTH. | | | A FIRE SUPPRESSION SYSTEM IS REQUIRED. | | | SEPARATE PLANS AND PERMITS REQUIRED. | | | 2) HOW IS SPRAY BOOTH GROUNDED. | | | 3) MORE DETAILS NEEDED ON FILTER PLANNED | | | FOR USE. FILTERS ARE REQUIRED TO COMPLY | | | WITH CERTAIN CRITERIA. | | | 4) NO DETAILS PROVIDED ON FIREWRAP | | | MATERIAL NOTED ON DUCT DIAGRAM. | | | 5) PLEASE CLEARLY NOTE ON THE PLANS | | | THAT THE EXHAUST DUCT EXTENDS AT LEAST | | | SIX FEET ABOVE THE ROOF. | | | 6) CLEARLY NOTE THE REQUIRED 3 FEET | | | LOCATED FOR AROUND THE SPRAY BOOTH. | | | 7) WHAT WILL THE SPRAY BOOTH BE USED | | | FOR. | | | 8) ARE THERE ANY FLAMMABLE LIQUID | | | CABINETS PLANNED FOR THE AREA. | | | | | | MIKE CARSILLO, CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|