| Plan Review Notes For Permit 01080131 |
| Permit Number |
01080131 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-04 00:00:00 | ************ UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE NOT | | | COMPLETELY CLEAR TO DO PLAN REVIEW. | | | RISER DIAGRAM SHOWS VERY FAINT AS OTHER | | | ITEMS ON PLANS. | | | | | | PLEASE CLOUD/TRIANGLE REVISIONS/CHANGES | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|