Plan Review Notes
Plan Review Notes For Permit 01080116
Permit Number 01080116
Review Stop P
Sequence Number 4
Notes
Date Text
2003-11-01 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) NEW RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. THE NEW SINK ON THE SANT
 RISER DIAGRAM SHALL BE SHOWN ON THE
 FLOOR PLAN. PLEASE SUBMIT A REVISION FOR
 THE FLOOR PLAN ALSO. SECTION 104.2.1
 2) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. LICENSE NUMBER NOT SHOWN
 PLEASE SEE THIS HAS BEEN THE SAME
 COMMENT ON MANY PREVIOUS REVIEWS. WE ARE
 NOW RETAINING ONE SET OF PLANS TO BE
 FILED AND TURNED INTO THE FBPE FOR THIS
 VIOLATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]