| 2003-08-08 00:00:00 | *************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE THAT REDLINES FROM |
| | ORIG REVIEW TWO YEARS AGO HAVE NOT BEEN |
| | CHANGED. PLEASE SEE GROUNDING ELECTRODE |
| | SYSTEM STILL REF'S 96 NEC. THIS WAS |
| | PERMITTED UNDER THE 99 NEC. PLEASE |
| | CHANGE ALLNEC CODE ARTS ACCORD. |
| | |
| | 2)NOTE: PLEASE SEE 220 FOR MIN KW FOR |
| | RANGE. PLEASE ADJUST LOAD CALCULATIONS. |
| | |
| | 3)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210-52. SEEMS TO HAVE AN OLD DOORWAY |
| | CLOSED UP WHICH BRINGS ON NEXT COMMENT |
| | FOR BDEROOM #4. |
| | |
| | 4)NOTE: PLEASE SEE MISSING SD REQ'D |
| | OUTSIDE BEDRM #4 |
| | |
| | 5)NOTE: PLEASE SEE 210-52C, 1,2,3,4,5 |
| | FOR KITCHEN COUNTER RECEPTS. PLEASE |
| | SEE PENINSULAR AND SEPARATE SPACES. |
| | |
| | 6)NOTE: PLEASE SEE 210-8 FOR ALL REQ'D |
| | GFI/GFI PROTECTED RECEPTS. GARAGE/ OUT- |
| | -SIDE ETC. |
| | |
| | 7)NOTE: PLEASE SEE 210-70 FOR CONTROL |
| | OF EGRESS LIGHTING TO BCAK PORCH AREA. |
| | PLEASE SHOW HOW AND WHERE LTS ARE |
| | TURNED ON AND OFF??? |
| | |
| | 8)NOTE: PLEASE SEE RISER DIAGRAM, |
| | SHOWS PANEL AS BEING A 8/16 CIRCUIT |
| | PANEL AND YET PANEL SCHEDULE SHOWS A |
| | 44-45 CIRCUIT PANEL?? PLEASE NOTE, PANEL |
| | DO NOT AND ARE NOT MADE W/ MORE THAN |
| | 42 CIRCUITS? 384-15 |
| | PLEASE SHOW REVISED RISER DIAGRAM AND |
| | PLEASE SHOW LOCATION OF SERVICE AND |
| | METER ON PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REIVEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |