Plan Review Notes
Plan Review Notes For Permit 01080116
Permit Number 01080116
Review Stop E
Sequence Number 4
Notes
Date Text
2003-08-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE THAT REDLINES FROM
 ORIG REVIEW TWO YEARS AGO HAVE NOT BEEN
 CHANGED. PLEASE SEE GROUNDING ELECTRODE
 SYSTEM STILL REF'S 96 NEC. THIS WAS
 PERMITTED UNDER THE 99 NEC. PLEASE
 CHANGE ALLNEC CODE ARTS ACCORD.
  
 2)NOTE: PLEASE SEE 220 FOR MIN KW FOR
 RANGE. PLEASE ADJUST LOAD CALCULATIONS.
  
 3)NOTE: PLEASE SEE MISSING RECEPTS PER
 210-52. SEEMS TO HAVE AN OLD DOORWAY
 CLOSED UP WHICH BRINGS ON NEXT COMMENT
 FOR BDEROOM #4.
  
 4)NOTE: PLEASE SEE MISSING SD REQ'D
 OUTSIDE BEDRM #4
  
 5)NOTE: PLEASE SEE 210-52C, 1,2,3,4,5
 FOR KITCHEN COUNTER RECEPTS. PLEASE
 SEE PENINSULAR AND SEPARATE SPACES.
  
 6)NOTE: PLEASE SEE 210-8 FOR ALL REQ'D
 GFI/GFI PROTECTED RECEPTS. GARAGE/ OUT-
 -SIDE ETC.
  
 7)NOTE: PLEASE SEE 210-70 FOR CONTROL
 OF EGRESS LIGHTING TO BCAK PORCH AREA.
 PLEASE SHOW HOW AND WHERE LTS ARE
 TURNED ON AND OFF???
  
 8)NOTE: PLEASE SEE RISER DIAGRAM,
 SHOWS PANEL AS BEING A 8/16 CIRCUIT
 PANEL AND YET PANEL SCHEDULE SHOWS A
 44-45 CIRCUIT PANEL?? PLEASE NOTE, PANEL
 DO NOT AND ARE NOT MADE W/ MORE THAN
 42 CIRCUITS? 384-15
 PLEASE SHOW REVISED RISER DIAGRAM AND
 PLEASE SHOW LOCATION OF SERVICE AND
 METER ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REIVEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW