Plan Review Notes
Plan Review Notes For Permit 01080053
Permit Number 01080053
Review Stop M
Sequence Number 2
Notes
Date Text
2001-08-27 00:00:00*****************PROVISO****************
  
  
 PRIOR COMMENTS ADDRESSED EXCEPT
 PERMISSIBLE REFRIGERANT QUANTITY,
 BUILDING VOLUME (CALC) SHALL BE THAT OF
 THE MEZZANINE NOT THE ENTIRE BUILDING
 AS PER 1997 SMC 1104.3.1.REPONSE -
 WILL BE ADDRESSED BY HILL PHOENIX DWGS
 TO BE SUBMITTED AT A LATER DATE.
 REFRIGERATION TO BE ON SEPARATE PERMIT.
  
 CALLED CONTRACTOR 8-27-01, LEFT MESSAGE,
 NEED A CONFIRMATION THAT REFRIG. WILL BE
 ON SEPARATE PERMIT.