2001-08-16 00:00:00********************DENIED**************
  
  
 PLAN SHEET R-1 PERMISSIBLE REFRIGERANT
 QUANTITY, BUILDING VOLLUME SHALL BE
 THAT OF THE MEZZANINE NOT THE ENTIRE
 BUILDING AS PER 1997 SMC 1104.3.1.
  
 PLEASE PROVIDE MANUFACTURER INFORMATION
 ON EMERGENCY GENERATOR.
  
 PLEASE PROVIDE AIR BALANCE SCHEDULE TO
 SHOW COMPLIANCE WITH 1997 SMC 501.2.
  
  
 ADDITIONAL PLANS AND PERMITS REQUIRED
 FOR HOOD, FIRE SUPRESSION AND WALK-IN
 COOLER/FREEZER SUBMIT PLANS AND
 MANUFACTURER SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
  