| Plan Review Notes For Permit 01080053 |
| Permit Number |
01080053 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-16 00:00:00 | ********************DENIED************** | | | | | | | | | PLAN SHEET R-1 PERMISSIBLE REFRIGERANT | | | QUANTITY, BUILDING VOLLUME SHALL BE | | | THAT OF THE MEZZANINE NOT THE ENTIRE | | | BUILDING AS PER 1997 SMC 1104.3.1. | | | | | | PLEASE PROVIDE MANUFACTURER INFORMATION | | | ON EMERGENCY GENERATOR. | | | | | | PLEASE PROVIDE AIR BALANCE SCHEDULE TO | | | SHOW COMPLIANCE WITH 1997 SMC 501.2. | | | | | | | | | ADDITIONAL PLANS AND PERMITS REQUIRED | | | FOR HOOD, FIRE SUPRESSION AND WALK-IN | | | COOLER/FREEZER SUBMIT PLANS AND | | | MANUFACTURER SUBMITTAL DATA WITH PERMIT | | | APPLICATION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|