Plan Review Notes
Plan Review Notes For Permit 01080053
Permit Number 01080053
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) EXIT REQUIREMENTS ON PAGE AB-1
 INDICATES 250 FEET TRAVEL DISTANCE
 PERMITTED. THE CURRENT FIRE CODE IS
 MORE RESTRICTIVE AT 150 FEET AND SHOULD
 BE NOTED ON THE PLANS.
 3) VERIFY EXISTING SLIDING DOORS MEET
 THE REQUIREMENTS FOR POWER OPERATED
 DOORS. PLEASE SEE 1985 EDITION OF THE
 LIFE SAFETY CODE SECTION 5-2.1.9.1.
 PLEASE EXPLAIN NOTE ON PLANS 105".
 4) PLEASE BE ADVISED THAT THIS BUILDING
 IS WITHIN THE CITY FIRE LIMITS. CERTAIN
 RESTRICTIONS APPLY TO THIS LOCATION.
 5) VERIFY IF A KNOX-BOX HAS BEEN
 INSTALLED FOR THE SHELL BUILDING.
 6) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 7) PROVIDE SEPARATE PLANS AND PERMITS
 FOR HOOD, DUCT AND EXTINGUISHING
 SYSTEMS.
 8) GAS INSTALLATION TO COMPLY WITH
 NFPA 54 AND SHOULD BE NOTED ON THE
 PLANS.
 9) PLEASE PROVIDE MORE DETAILS ON
 NATURAL GAS GENERATOR PLANNED FOR USE.
 10) KITCHEN EXHAUST DUCT TO BE AT LEAST
 40 INCHES ABOVE THE ROOF.
 11) PLEASE CLEARLY IDENTIFY ALL
 EMERGENCY LIGHT FIXTURE LOCATIONS.
 12) DUCT SMOKE DETECTORS TO CAUSE AIR
 HANDLER SHUT DOWN AND ACTIVATE FIRE
 ALARM SYSTEM.
 13) NO FIRE SPRINKLER SYSTEM DRAWINGS
 PROVIDED.
 14) WRITTEN PERMISSION NEEDED TO MOUNT
 FIRE ALARM SIGNALING DEVICES ON THE
 CEILING NEEDED FROM THIS OFFICE.
 15) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM INSTALLATION. CUT
 SHEETS, WIRING DIAGRAM AND BATTERY
 CALCULATIONS REQUIRED AT TIME OF
 SUBMITTAL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910