| 2001-08-02 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY |
| | CODE 3343-00. |
| | 2) EXIT REQUIREMENTS ON PAGE AB-1 |
| | INDICATES 250 FEET TRAVEL DISTANCE |
| | PERMITTED. THE CURRENT FIRE CODE IS |
| | MORE RESTRICTIVE AT 150 FEET AND SHOULD |
| | BE NOTED ON THE PLANS. |
| | 3) VERIFY EXISTING SLIDING DOORS MEET |
| | THE REQUIREMENTS FOR POWER OPERATED |
| | DOORS. PLEASE SEE 1985 EDITION OF THE |
| | LIFE SAFETY CODE SECTION 5-2.1.9.1. |
| | PLEASE EXPLAIN NOTE ON PLANS 105". |
| | 4) PLEASE BE ADVISED THAT THIS BUILDING |
| | IS WITHIN THE CITY FIRE LIMITS. CERTAIN |
| | RESTRICTIONS APPLY TO THIS LOCATION. |
| | 5) VERIFY IF A KNOX-BOX HAS BEEN |
| | INSTALLED FOR THE SHELL BUILDING. |
| | 6) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION FOR WALLS |
| | AND CEILINGS. |
| | 7) PROVIDE SEPARATE PLANS AND PERMITS |
| | FOR HOOD, DUCT AND EXTINGUISHING |
| | SYSTEMS. |
| | 8) GAS INSTALLATION TO COMPLY WITH |
| | NFPA 54 AND SHOULD BE NOTED ON THE |
| | PLANS. |
| | 9) PLEASE PROVIDE MORE DETAILS ON |
| | NATURAL GAS GENERATOR PLANNED FOR USE. |
| | 10) KITCHEN EXHAUST DUCT TO BE AT LEAST |
| | 40 INCHES ABOVE THE ROOF. |
| | 11) PLEASE CLEARLY IDENTIFY ALL |
| | EMERGENCY LIGHT FIXTURE LOCATIONS. |
| | 12) DUCT SMOKE DETECTORS TO CAUSE AIR |
| | HANDLER SHUT DOWN AND ACTIVATE FIRE |
| | ALARM SYSTEM. |
| | 13) NO FIRE SPRINKLER SYSTEM DRAWINGS |
| | PROVIDED. |
| | 14) WRITTEN PERMISSION NEEDED TO MOUNT |
| | FIRE ALARM SIGNALING DEVICES ON THE |
| | CEILING NEEDED FROM THIS OFFICE. |
| | 15) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM SYSTEM INSTALLATION. CUT |
| | SHEETS, WIRING DIAGRAM AND BATTERY |
| | CALCULATIONS REQUIRED AT TIME OF |
| | SUBMITTAL. |
| | |