Plan Review Notes
Plan Review Notes For Permit 01080053
Permit Number 01080053
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-14 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT MEANS OF
 DISCONNECT WILL NEED TO MEET 230-72.
 PLEASE NOTE THAT RISER NOTES SHOWN AS
 #3 ON E-7 MENTIONS SHUNT TRIP FOR MAIN.
 PLEASE NOTE THAT A MANUAL MEANS OF
 DISCONNECT IS REQ`D PER 230-76 AND
 230-79.
  
 2)NOTE: PLEASE NOTE THAT PER NOTE FOR
 LOCATION OF GENERATOR SHUT DOWN,,,
 SHUT DOWN OF GEN. NEEDS TO BE GROUPED
 W/ MAIN.
  
 3)NOTE: PLEASE NOTE PROVIDE
 CLARIFICATION FOR FIRE PUMP AND FIRE
 PUMP FEED?
  
  
 PLEASE PROVIDE THE ABOVE CLARIFICATION
 AND SUBMIT FOR REVIEW. PLEASE NOTE ALL
 FIRE DEPT COMMENTS AS THEY MAY PERTAIN
 TO ELECTRICAL AS WELL. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372