2001-08-17 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01080053
 375 S ROSEMARY
 "PUBLIX"
  
 NOTE:FIRE DISTRICT
 EXISTING DOORS 1E,2E & 3E ARE HORIZONTAL
 SLIDING DOORS, THEY ARE TO COMPLY WITH
 SBC SEC 1012.4 FOR HORIZONTAL SLIDING
 DOORS.
  
 1)- ENERGY CALCULATIONS?
  
 2)- SBC104.2.2. MEZZANINE FLOOR PLAN,
 WHERE DOES THE DOORS 33-N LEAD TO? WHAT
 STOPS SOMEONE FROM OPENING THESE DOORS
 AND FALLING?
  
 3)- SHEET A-11 DOOR LEADING INTO THE
 MENS RESTROOM REQUIRES 18" ON THE LATCH
 SIDE OF THE DOOR PULL SIDE( FL ACC CODE
 4.13.6)
  
 4)- FL ACC CODE 4.5 GROUD & FLOOR SUR-
 FACES ALONG ACCESSIBLE ROUTES AND IN ACC
 ESSIBLE ROOMS AND SPACES INCLUDING
 FLOORS, WALKS, RAMPS, STAIRS AND CURB
 RAMPS, SHALL BE FIRM, SLIP RESISTANT &
 STABLE.A STATIC COEFFICIENT OF FRICTION
 OF 0.6 IS RECOMMENDED FOR ACCESSIBLE
 ROUTES & 0.8 FOR RAMPS.
  
 5)- SBC 803.3 MISSING IS A MINIMUM INTER
 IOR FINISH CLASSIFICATION SCHEDULE, SEE
 SBC TABLE 803.3. FOR MAX. SMOKE/ FLAME
 SPREAD.
 SBC 903.7.1 AN APPROVED AUTOMATIC SPRINK
 LER SYSTEM SHALL BE PROVIDED IN STORES
 AND SIMILAR OCCUPANCIES WHERE STTOCKS OF
 COMBUSTIBLE MATERIALS ARE ON DISPLAY FOR
 PUBLIC SALE AND WHERE THE STORY FLOOR
 AREA EXCEEDS 15,000 SQ. FT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412