| 2001-08-07 00:00:00 | ***************UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT THERE IS NO | | | BRKR SIZE SHOWN FOR "MAIN" OF PANEL "B". | | | | | | 2)NOTE: PLEASE NOTE THAT CODE ART SHOWN | | | FOR GROUNDING ELECTRODE SYSTEM IS SHOWN | | | FORM THE "96" NEC. WE ARE UNDER THE | | | "99" NEC . PLEASE CORRECT. | | | PLEASE SUBMIT CLARIFICATION ON | | | REINFORCING STEEL? PLEASE CLARIFY WHERE | | | THE BLDGSTEEL IS? PLANS SHOW SERVICES | | | ON STAND | | | ALONE RISERS. | | | | | | 3)NOTE: PLEASE CLARIFY LOAD SHOWN AT | | | 250%? AND LOAD IS 125%. MUST BE A | | | MISPRINT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|