Plan Review Notes
Plan Review Notes For Permit 01080021
Permit Number 01080021
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-07 00:00:00***************UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THERE IS NO
 BRKR SIZE SHOWN FOR "MAIN" OF PANEL "B".
  
 2)NOTE: PLEASE NOTE THAT CODE ART SHOWN
 FOR GROUNDING ELECTRODE SYSTEM IS SHOWN
 FORM THE "96" NEC. WE ARE UNDER THE
 "99" NEC . PLEASE CORRECT.
 PLEASE SUBMIT CLARIFICATION ON
 REINFORCING STEEL? PLEASE CLARIFY WHERE
 THE BLDGSTEEL IS? PLANS SHOW SERVICES
 ON STAND
 ALONE RISERS.
  
 3)NOTE: PLEASE CLARIFY LOAD SHOWN AT
 250%? AND LOAD IS 125%. MUST BE A
 MISPRINT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372