| Plan Review Notes For Permit 01080004 |
| Permit Number |
01080004 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-13 00:00:00 | DENIED | | | | | | 1) PLUMBING FIXTURES REQUIRE 7'6" | | | MINIMUM. ONLY 6'0" SHOWN. PER SPC-94 | | | SEC.403.4 | | | | | | 2) SHOWERS ARE REQUIRED TO HAVE PRIVACY | | | SCREENS PER SPC-94 SEC 404.3 | | | | | | 3) SEPARATE BUILDING DRAINS REQUIRE A | | | SEPARATE 3" VENT PER SPC-94 SEC 904.3.1 | | | | | | 4) MINIMUM SHOWER SIZE IS 30" AND IS | | | MEASURED FROM THE FINISHED INTERIOR | | | DIMENSIONS AT A HEIGHT EQUAL TO THE TOP | | | OF THE CURB. SBC-97 CHAPTER 29 | | | | | | 5) NO HUB COUPLINGS NOT APPROVED FOR | | | PVC INSTALLATION. | | | | | | 6) TUB DRAIN NOT VENTED PROPERLY. CAN | | | NOT BE TAKEN OFF BELOW WATER CLOSET. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|