| Date |
Text |
| 2001-10-12 00:00:00 | *******************PROVISO************** |
| | |
| | |
| | ADDITIONAL PERMITS REQUIRED FOR HOOD, |
| | FIRE SUPRESSION AND WALK-IN COOLERS. |
| | PLEASE PROVIDE PLANS WITH PERMIT |
| | APPLICATION. |
| | |
| | TERMINATION FOR HOOD EXHAUST SHALL |
| | COMPLY WITH 1997 SMC 506.1. |
| | |
| | 1.SHALL BE LOCATED 10' FROM ANY |
| | ADJACENT BUILDING, PARKING AREA, |
| | ADJACENT PROPERTY LINE, AS WELL AS |
| | ANY WINDOW DOOR OR AIR INTAKE. |
| | |
| | 2.EVERY EXHAUST OUTLET WHICH IS |
| | LOCATED ABOVE THE ROOF SHALL |
| | TERMINATE AT LEAST 40" ABOVE THE |
| | ROOF SURFACE. |
| | |
| | THE DISTANCE FROM THE FLOOR TO THE |
| | BOTTOM EDGE OF THE HOOD IS NOT LEGIBLE |
| | ON PLAN.AS PER 1997 SMC 504.2 #2 THIS |
| | DISTANCE SHALL BE A MAXIMUM OF 7'. |
| | |
| | NOTE:REFERENCE THE CONDENSER UNIT |
| | STANDS.COMMENTS FROM 8/20/01 |
| | WERE NOT ADDRESSED IN THE |
| | RESUBMITTAL.A MINIMUM OF 18" |
| | IS REQUIRED BETWEEN THE ROOF |
| | SURFACE TO THE BOTTOM OF THE |
| | SUPPORT RAIL. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 EXT. |
| | 8388. |