Plan Review Notes
Plan Review Notes For Permit 01071546
Permit Number 01071546
Review Stop P
Sequence Number 1
Notes
Date Text
2001-08-15 00:00:00DENIED;
 1.GREASE TRAP TO BE SIZED BY WEST PALM
 BEACH UTILITYS DEPARTMENT. CONTACT
 RODNEY COMPO AT 837-4074.
 2.SHOW COMPLIANCE WITH 94 SPC TABLE 407
 MINIMUM PLUMBING FACILITIES. SEE SEC.
 407.1.3 FOR DEDUCTABLE AREA.
 3.PAGE P-1 WATER RISER DIAGRAM, SIZE
 PIPES.
 4.SHOW ON WATER RISER WHERE WATER HAMMER
 ARRESTERSARE TO BE INSTALLED.SPECIFY
 TYPE AND SIZE. TO BE INSTALLED PER
 MANUFACTORS RECOMMENDATIONS AND SPC
 SEC. 607.8.2 AND 607.8.3.
 5.NOTE 13 WASTE PIPING LESS THAN 3" TO
 HAVE A PITCH OF 1/4" PER FOOT PER. SEC
 705.2
 6.NOTE 14 DIELECTRIC COUPLINGS ARE NOT
 PERMITED IN CITY WATER SYSTEM.
 7.NOTE 8 GALVANIZED WATER PIPE IS NOT
 PERMITED IN CITY WATER SYSTEM.
 8.THREE COMPARTMENT SINK SHALL DISCHARGE
 INDIRECTLY INTO A FLOOR SINK. SEC.
 804.1.
 9.( SANITARY RISER DIAGRAM)
 A.SHOW 3" VENT TO OUT SIDE.
 B.2 FLOOR SINKS ARE MISSING FROM
 DIAGRAM.
 C.WHAT DO DOTTED LINES MEAN? (STEAM
 TABLE TO FLOOR DRAIN. FLOOR SINK
 TO FLOOR DRAIN)
 10.GAS RISER DIAGRAM. NOT ENOUGH INFOR-
 MATION. AUTOMATIC SHUTOFF VALVE TO
 BE INSTALLED WITH HOOD SYSTEM. SHOW
 ON DRAWINGS AND ON RISER DIAGRAM. SEE
 INFORMATION SHEET. PLEASE COMPLY WITH
 NUMBER HIGHLIGHTED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369