| Plan Review Notes For Permit 01071546 |
| Permit Number |
01071546 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-20 00:00:00 | DENIED: | | | 1. HOOD EXHAUST TERMINATION DOES NOT | | | COMPLY WITH 1997 SMC 506.1 PROVIDE | | | INFORMATION SHOWING MINIMUM 10' FROM | | | ANY ADJACENT PROPERTY LINE PARKING | | | AREA, AIR INTAKE, WINDOW, OR DOOR. | | | 2. NO INFORMATION PROVIDED FORAIR | | | CONDITIONING SYSTEM. | | | 3. NOTE SEPARATE PERMITS WILL BE | | | REQUIRED FOR HOOD, SUPPRESSION SYSTEM | | | AND WALK IN COOLERS. PROVIDE PLANS AT | | | TIME OF PERRMIT APPLICATION FOR THIS | | | WORK. | | | 4. MINIMUM CLEARANCE FROM BOTTOM OF | | | SUPPORT BEAM OF STAND TO FINISHED ROOF | | | SURFACE TO BE 18". |
|