Plan Review Notes
Plan Review Notes For Permit 01071546
Permit Number 01071546
Review Stop M
Sequence Number 1
Notes
Date Text
2001-08-20 00:00:00DENIED:
 1. HOOD EXHAUST TERMINATION DOES NOT
 COMPLY WITH 1997 SMC 506.1 PROVIDE
 INFORMATION SHOWING MINIMUM 10' FROM
 ANY ADJACENT PROPERTY LINE PARKING
 AREA, AIR INTAKE, WINDOW, OR DOOR.
 2. NO INFORMATION PROVIDED FORAIR
 CONDITIONING SYSTEM.
 3. NOTE SEPARATE PERMITS WILL BE
 REQUIRED FOR HOOD, SUPPRESSION SYSTEM
 AND WALK IN COOLERS. PROVIDE PLANS AT
 TIME OF PERRMIT APPLICATION FOR THIS
 WORK.
 4. MINIMUM CLEARANCE FROM BOTTOM OF
 SUPPORT BEAM OF STAND TO FINISHED ROOF
 SURFACE TO BE 18".