Plan Review Notes
Plan Review Notes For Permit 01071497
Permit Number 01071497
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-08-09 00:00:00FAILED:
 1. PLEASE PROVIDE ADDITIONAL INFORMATION
 FOR THE PILES AND INDICATE THE SIZE,
 DESIGN LOADS, EXISTING, NEW,ETC..
 2. THE ENGINEER OF RECORD MUST SHOW THAT
 THE PILES AS SHOWN CAN CARRY THE LOADS
 AND THAT THEY ARE STRUCTURALLY ADEQUATE.
 3. CONTRACTOR MUST OBTAIN, FROM ALL
 OTHER FEDERAL, STATE AND LOCAL
 PERMITTING AGENCIES, THE OTHER NECESSARY
 AND REQUIRED PERMIT BEFORE COMMENCING
 THE PROJECT.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI