| Plan Review Notes For Permit 01071485 |
| Permit Number |
01071485 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2002-03-19 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE FOLLOWING | | | PANEL SCHEDULES NEED TO BE SUBMITTED FOR | | | REVIEW.EHP-6/EHP-7/ELP6A/ELP7A. | | | | | | 2)NOTE: PLEASE NOTE THAT THE FOLLOWING | | | ITEMS ON ONE-LINE DIAGRAM NEED TO MATCH/ | | | CORRELATE WITH ALL PANEL SCHEDULES. | | | NEC-215-5 | | | DPH2, 4ITEMS. | | | DPH1, MAIN | | | MSB1, DISC #3 | | | DPH4, MAIN | | | DPL4, MAIN AND 4TH BRKR | | | DPL3, 4TH BRKR | | | HP3,2 ITEMS | | | MSB-2, PANEL S2?, EMDP-1 | | | HP8, 2 BRKRS | | | LP8, 3 BRKRS | | | EMDP1, EMCC1,ELEV, 1&5,EHP6 | | | MSB-3, 6 MAIN BRKRS | | | MCC2, MAIN AND OTHER MAIN BRKRS | | | MCC1, 4 BRKRS, AND AHU 15/16 | | | MCC3, 4BRKRS. | | | | | | PLEASE NOTE THAT MOST OF THE ABOVE HAVE | | | SOME DIFFERENCES ON PANEL SCHEDULES. | | | PLEASE ALSO NOTE THAT THERE MAY BE OTHER | | | -S THAT WERE NOT LOCATED, PLEASE GO | | | OVER PLANS. | | | | | | 3)NOTE: PLEASE PROVIDE A LOAD SUMMARY | | | FOR GENERATOR, SINCE GEN SIZE HAS BEEN | | | DECREASED. | | | | | | 4)NOTE: PLEASE HAVE PERMIT VALUATION | | | INCREASED DUE TO CONTRACT INCREASES. | | | PLEASE VERIFY AMOUNTS. CITY-WIDE ADMIN | | | CODE.104.7.5 (1997) EDITION. | | | | | | 5)NOTE: PLEASE SUBMIT REVISIONS FROM | | | PREVIOUS REVIEW THAT WERE NOT SUBMITTED | | | BACK FOR STAMPING. THE FLOOR LAYOUTS | | | DID NOT HAVE ANY COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE NAY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|