Plan Review Notes
Plan Review Notes For Permit 01071485
Permit Number 01071485
Review Stop M
Sequence Number 5
Notes
Date Text
2001-11-14 00:00:00THE FOLLOWING ITEMS NED TO BE CLARIFIED:
  
 1. M2.207 FIRE DAMPER REQUIRED FOR
 TRANSFER OPENING IN ELEC. RM 2E-16 WEST
 WALL BY COLUMN 16 AND S.
 2. WHAT TYPE OF FUEL SUPPLY IS TO BE
 USED FOR THE GENERATOR AND HOW MUCH ON
 SITE STORAGE?
 3. WALLS REQUIREING RATING SHALL HAVE
 OPENING PROTECTION PER 1997 SMC 610.
 4. NFPA 37 CH 5 REQUIRES RATING OF
 GEERATOR RM WALLS.
 5. PLAN SHOWS 2 HR RATING OF GENERATOR
 RM WALLS.
 6 CAN WE ACCEPT THE HOWE REPORT FOR
 SMOKE CONTROL IF NOT SIGNED/ SEALED BY
 STATE OF FLORIDA ENGINEER.