Plan Review Notes
Plan Review Notes For Permit 01071485
Permit Number 01071485
Review Stop E
Sequence Number 5
Notes
Date Text
2002-02-22 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THERE ARE ANY PANELS
 THAT THE LOADS WERE NOT REVISED WHEN
 LOADS WERE ADDED.
 PLEASE SEE;
 "EHP1"
 "EHP2"
 "EHP3"
 "LP-5
 "LP-7"
 "LP-8"
 "EHP6"
 "EMCC-1"
  
 PLEASE NOTE THAT "MCC4" ALSO DOES NOT
 HAVE ALL LOADS REVISED.
 PLEASE NOTE THAT LOAD FOR "MSB3" WAS
 NOT REVISED.
 PLEASE NOTE LOAD FOR "MCC-1" ALSO NEEDS
 TO BE REVISED.
 PLEASE NOTE THAT PANEL SCHEDULE NEED TO
 BE REVISED. PLEASE NOTE LOAD SHOWN
 ON MSB-3 ALREADY IS AT 3417AMPS.
  
 2)NOTE: PLEASE NOTE THAT ONE LINE SHOWS
 AHU#15 AT 60HP AND "MCC1" SHOWS AT 50HP
 AND LOAD FOR HP. PLEASE CORRELATE.
  
 3)NOTE: PLEASE E6.109 LP-8 25,27,29
 SHOWS 60A AND E2.202 SHOWS 30A. PLEASE
 CORRELATE.
  
 4)NOTE: PLEAS SUBMIT LINE DIAGRAM THAT
 WOULD INCLUDE LP-8.
  
  
 PLEASE REVISE AND SUBMIT ALL OF THE
 ABOVE INFORMATION FOR REVIEW. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372