| Plan Review Notes For Permit 01071485 |
| Permit Number |
01071485 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2002-02-22 00:00:00 | ******************* UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THERE ARE ANY PANELS | | | THAT THE LOADS WERE NOT REVISED WHEN | | | LOADS WERE ADDED. | | | PLEASE SEE; | | | "EHP1" | | | "EHP2" | | | "EHP3" | | | "LP-5 | | | "LP-7" | | | "LP-8" | | | "EHP6" | | | "EMCC-1" | | | | | | PLEASE NOTE THAT "MCC4" ALSO DOES NOT | | | HAVE ALL LOADS REVISED. | | | PLEASE NOTE THAT LOAD FOR "MSB3" WAS | | | NOT REVISED. | | | PLEASE NOTE LOAD FOR "MCC-1" ALSO NEEDS | | | TO BE REVISED. | | | PLEASE NOTE THAT PANEL SCHEDULE NEED TO | | | BE REVISED. PLEASE NOTE LOAD SHOWN | | | ON MSB-3 ALREADY IS AT 3417AMPS. | | | | | | 2)NOTE: PLEASE NOTE THAT ONE LINE SHOWS | | | AHU#15 AT 60HP AND "MCC1" SHOWS AT 50HP | | | AND LOAD FOR HP. PLEASE CORRELATE. | | | | | | 3)NOTE: PLEASE E6.109 LP-8 25,27,29 | | | SHOWS 60A AND E2.202 SHOWS 30A. PLEASE | | | CORRELATE. | | | | | | 4)NOTE: PLEAS SUBMIT LINE DIAGRAM THAT | | | WOULD INCLUDE LP-8. | | | | | | | | | PLEASE REVISE AND SUBMIT ALL OF THE | | | ABOVE INFORMATION FOR REVIEW. IF THERE | | | ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|