2001-10-12 00:00:00****ATRIUM SMOKE CONTROL****************
  
 THE FOLLOWING QUESTIONS NEED TO BE
 ADDRESSED .
 1. WHY NOT USE MANUAL PULL TO INITIATE
 ATRIUM SMOKE CONTROL SYSTEM?
 2. PAGE 19 OF 57 ZONE 3 SHOWS A 6 FT
 HEIGHT FOR SMOKE FOR THE GRADE LEVEL
 AND FOR THE BALLROOM PREFUNCTION AREA.
 THIS CONFLICTS WITH PRIOR STATEMENTS TO
 MAINTAIN A 10 FOOT TENABLE HEIGHT.
 3. PAGE 30 SHOWS NO SMOKE BEING USED AND
 PAGE 34 INDICATES A SMOKE PRODUCTION
 METHOD. BE ADVISED THE ACCEPTANCE
 TEST WILL REQUIRE SMOKE TO BE USED AS
 PART OF THE CRITERIA TO ACCEPT THE
 SMOKE CONTROL SYSTEM.
 4.PROVIDE A DIAGRAM OF THE SMOKE CONTROL
 PANEL FOR REVIEW.
 5. PROVIDE A COPY OF THE FINAL APPROVED
 CITY STAMPED ANALYSIS OF SMOKE CONTROL/
 SMOKE EXHAUST PRIOR TO THE ACCEPTANCE
 TEST FOR INSPECTORS REVIEW.