| 2001-10-12 00:00:00 | ****ATRIUM SMOKE CONTROL**************** | | | | | | THE FOLLOWING QUESTIONS NEED TO BE | | | ADDRESSED . | | | 1. WHY NOT USE MANUAL PULL TO INITIATE | | | ATRIUM SMOKE CONTROL SYSTEM? | | | 2. PAGE 19 OF 57 ZONE 3 SHOWS A 6 FT | | | HEIGHT FOR SMOKE FOR THE GRADE LEVEL | | | AND FOR THE BALLROOM PREFUNCTION AREA. | | | THIS CONFLICTS WITH PRIOR STATEMENTS TO | | | MAINTAIN A 10 FOOT TENABLE HEIGHT. | | | 3. PAGE 30 SHOWS NO SMOKE BEING USED AND | | | PAGE 34 INDICATES A SMOKE PRODUCTION | | | METHOD. BE ADVISED THE ACCEPTANCE | | | TEST WILL REQUIRE SMOKE TO BE USED AS | | | PART OF THE CRITERIA TO ACCEPT THE | | | SMOKE CONTROL SYSTEM. | | | 4.PROVIDE A DIAGRAM OF THE SMOKE CONTROL | | | PANEL FOR REVIEW. | | | 5. PROVIDE A COPY OF THE FINAL APPROVED | | | CITY STAMPED ANALYSIS OF SMOKE CONTROL/ | | | SMOKE EXHAUST PRIOR TO THE ACCEPTANCE | | | TEST FOR INSPECTORS REVIEW. |
|