| Plan Review Notes For Permit 01071485 |
| Permit Number |
01071485 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-11-07 00:00:00 | | | | SUSPENDED CEILING SUBMITTAL | | | | | | IS DENIED FOR THE FOLLOWING REASONS: | | | | | | 1] | | | ALL CALCULATIONS AND ACCOMPANYING | | | DRAWINGS SHALL BE SIGNED AND SEALED BY | | | P.E. WARDEN. | | | | | | 2] | | | SUBMIT ANCHORING DETAILS FOR WIRE AT | | | EXSISTING SUPPORTING STRUCTURE. SUBMIT | | | SUPPORTING DOCUMENTATION TO CLARIFY #8 | | | WIRES CAPACITY,NOTE ON CALCULATION | | | SHEET 'PROBABLY ADEQUATE' IS NOT | | | SUFFICIENT. | | | | | | 3] | | | PROVIDE THICKNESS AND SPEC. ON WELD FOR | | | ALUMINUM ANGLE. | | | | | | | | | | | | | | | LUIS MARTINEZ | | | 805-6710 | | 2003-01-09 00:00:00 | PROCESS SHOP DRAWINGS APPROVED ON 12/26 |
|