Plan Review Notes
Plan Review Notes For Permit 01071485
Permit Number 01071485
Review Stop B
Sequence Number 4
Notes
Date Text
2003-11-07 00:00:00 
 SUSPENDED CEILING SUBMITTAL
  
 IS DENIED FOR THE FOLLOWING REASONS:
  
 1]
 ALL CALCULATIONS AND ACCOMPANYING
 DRAWINGS SHALL BE SIGNED AND SEALED BY
 P.E. WARDEN.
  
 2]
 SUBMIT ANCHORING DETAILS FOR WIRE AT
 EXSISTING SUPPORTING STRUCTURE. SUBMIT
 SUPPORTING DOCUMENTATION TO CLARIFY #8
 WIRES CAPACITY,NOTE ON CALCULATION
 SHEET 'PROBABLY ADEQUATE' IS NOT
 SUFFICIENT.
  
 3]
 PROVIDE THICKNESS AND SPEC. ON WELD FOR
 ALUMINUM ANGLE.
  
  
  
  
 LUIS MARTINEZ
 805-6710
2003-01-09 00:00:00PROCESS SHOP DRAWINGS APPROVED ON 12/26