| 2001-10-12 00:00:00 | *******REVIEW DOES NOT INCLUDE SMOKE |
| | CONTROL SYSTEM************************* |
| | DENIED |
| | 1.M2.106 NO FIRE DAMPERS SHOWN IN RATED |
| | WALL DIFFUSER PENETRATIONS AT ALCOVE BY |
| | COLUMNS T AND U AND 8 AND 9. |
| | 2. FIRE DAMPER NOT SHOWN AT RATED WALL |
| | PENETRATION OF 16X18 DUCT BY |
| | COLUMN LINE 4 AND C.8 M2.201 |
| | 3. FIRE DAMPERS NOT SHOWN M2.202 AT |
| | PENETRATION OF 28 X 20 DUCT BY COLUMN G |
| | AND ( AND ELECTRIC ROOOM 14X 8 DUCT |
| | PENETRATION SAME AREA |
| | 4. M2.202 TELEPHONE ROOM 2N31 APPEARS TO |
| | AHVE RATED WALL PENETRATION BY 8X8 |
| | DUCT. |
| | 5.M2.208 NO FIRE DAMPERS SHOWN AT 2 DUCT |
| | PENETRATIONS BY COLUMN U AND 21 AND NO |
| | FIRE DAMPER SHOWN AT 18X 20 DUCT BY U |
| | AND 20. |
| | 6 M2.102 TRANSFER AIR NEEDS TO BE FROM |
| | SATELLITE ROOM AS WELL AS IN DOOR N40-1 |
| | 7. M 2.106 FIRE DAMPER REQUIRED IN 6" |
| | SUPPLY TO 1N68, SHOW MANAGERS OFFICE |
| | 8> M2.107 NO FIRE DAMPER SHOWN IN 16X6 |
| | TRANSFER DUCT IN STORAGE RM 1E-28 EAST |
| | WALL |
| | 9. PREVIOUS COMMENT ON VAULT ROOM |
| | OPENINGS REFER TO LOUVER OPENINGS IN |
| | REQUIRED RATED WALLS. THIS WOULD ALSO |
| | INCLUDE THE GENERATOR ROOM. |
| | 10. PLUMBING CONNECTION OF CONDENSATE |
| | DRAINS TO STORM SEWER TO BE PER |
| | PLUMBING APPROVAL. |
| | |
| | SEE MECH REVIEW # 4 FOR SMOKE CONTROL |
| | COMMENTS |