Plan Review Notes For Permit 01071485
Permit Number 01071485
Review Stop M
Sequence Number 3
Notes
Date Text
2001-10-12 00:00:00*******REVIEW DOES NOT INCLUDE SMOKE
 CONTROL SYSTEM*************************
 DENIED
 1.M2.106 NO FIRE DAMPERS SHOWN IN RATED
 WALL DIFFUSER PENETRATIONS AT ALCOVE BY
 COLUMNS T AND U AND 8 AND 9.
 2. FIRE DAMPER NOT SHOWN AT RATED WALL
 PENETRATION OF 16X18 DUCT BY
 COLUMN LINE 4 AND C.8 M2.201
 3. FIRE DAMPERS NOT SHOWN M2.202 AT
 PENETRATION OF 28 X 20 DUCT BY COLUMN G
 AND ( AND ELECTRIC ROOOM 14X 8 DUCT
 PENETRATION SAME AREA
 4. M2.202 TELEPHONE ROOM 2N31 APPEARS TO
 AHVE RATED WALL PENETRATION BY 8X8
 DUCT.
 5.M2.208 NO FIRE DAMPERS SHOWN AT 2 DUCT
 PENETRATIONS BY COLUMN U AND 21 AND NO
 FIRE DAMPER SHOWN AT 18X 20 DUCT BY U
 AND 20.
 6 M2.102 TRANSFER AIR NEEDS TO BE FROM
 SATELLITE ROOM AS WELL AS IN DOOR N40-1
 7. M 2.106 FIRE DAMPER REQUIRED IN 6"
 SUPPLY TO 1N68, SHOW MANAGERS OFFICE
 8> M2.107 NO FIRE DAMPER SHOWN IN 16X6
 TRANSFER DUCT IN STORAGE RM 1E-28 EAST
 WALL
 9. PREVIOUS COMMENT ON VAULT ROOM
 OPENINGS REFER TO LOUVER OPENINGS IN
 REQUIRED RATED WALLS. THIS WOULD ALSO
 INCLUDE THE GENERATOR ROOM.
 10. PLUMBING CONNECTION OF CONDENSATE
 DRAINS TO STORM SEWER TO BE PER
 PLUMBING APPROVAL.
  
 SEE MECH REVIEW # 4 FOR SMOKE CONTROL
 COMMENTS