| 2001-10-15 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - SGC-97 - FACBC-97 |
| | |
| | 1) GREASE TRAP, TYPE AND SIZE. CONTACT |
| | WPB RSTP, ENVIRONMENTAL COMPLIANCE. R |
| | COMPO (561) 837-4074 ORD #2938-96. |
| | PLEASE PROVIDE SEATING CAPACITY, BALL- |
| | ROOM HOLDS 3904. RESPONSE NOTED, BUT NOT |
| | ADDRESSED FROM PREVIOUS REVIEW. |
| | 2) SHTA1-7.1 - 7.2, PROVIDE CALCULATIONS |
| | FOR PRIMARY AND SECONDARY STORM DRAINS. |
| | SEC 1108 AND 1109 + 1/2 THE AREA OF THE |
| | VERTICAL WALLS, UPPER ROOFS DRAINING TO |
| | LOWER ROOFS TO BE INCLUDED. CALCULATIONS |
| | ARE REQUIRED TO CHECK PIPE SIZES. |
| | 3) SHT P1-1.1 AHU CONDENSATE DRAIN DE- |
| | TAIL, COMPLY W/SEC 104.2 & 104.3 PLANS & |
| | SPECS., PROVIDE AN ISOMETRIC DRAWING OF |
| | A COMMON A/C CONDENSATE SYSTEM, CONNECT- |
| | ED TO STORM DRAINAGE SYSTEM OUTSIDE OF |
| | BUILDING WITH A OVERFLOW VENT 6" ABOVE |
| | GRADE AS REQUESTED IN PREVIOUS REVIEW. |
| | 4) SHT P2-1.1 CONDENSATE TIED INTO STORM |
| | INSIDE BLDG AT INTERSECT. OF COLS B & 4 |
| | VOL III. |
| | 5) SHT P2-1.1 COMPLY W/SEC 714 MAXIMUM |
| | FIXTURE LOAD ON THE DWV SYSTEM. SHOW |
| | FIXTURE UNIT LOAD THROUGHOUT SYSTEM. SEC |
| | 104.2 (TALK TO GEORGE HAZAU) |
| | 6) SHT P2-1.3, CAN WASH & TRASH COMPACT- |
| | OR, CONNECT TO GREASE WASTE. LOCAL ORD |
| | #2938-96. STK DIAG. "H" SANT SHOWS CAN |
| | WASH STILL ON SANT. SHT P3-2.3 |
| | 7) SHT P3-2.2, STACK "D", "Q" PLBG. FIX- |
| | TURES FROM UPPER FLOORS SHALL NOT DIS- |
| | CHARGE INTO A BATTERY VENTED BRANCH. |
| | SHOW UPPER FLOOR DISCHARGING INTO SEPAR- |
| | ATE 4" LINE THAT FLOOR DRAINS ARE DRAIN- |
| | ING INTO. |
| | 8) SHTP3-2.1 THRU P3-2.4 STK DIAGRAMS. |
| | STK "D" ISOMETRIC DOES NOT MATCH FLAT |
| | DRAWING, FLOOR DRAIN BY D.F. ARE ALL FD |
| | VENTS TYPICAL IN REST ROOMS? |
| | 9) SHOP DRAWING SHALL BE PROVIDED FOR |
| | THE U/G UTILITY SERVICE BOX FROM THE |
| | MANUFACTURE TO SHOW HOW THERE IS NOT A |
| | CROSS CONNECTION OF WASTE AND POTABLE |
| | WATER SEC 601.5 AS REQUESTED IN PREVIOUS |
| | REVIEW. |
| | GAS PERMIT REQUIREMENTS |
| | 10) GAS ISOMETRIC ON SHT P4-1.3 HEADER |
| | IN KITCHEN TO BE UNIFORM. SHOWS 4" TO 3" |
| | TO 2-1/2" THEN BACK TO 4". ALSO SEDIMENT |
| | TRAP SHALL BE UPSTREAM OF EQUIPMENT NOT |
| | AND END OF LINE AS SHOWN. |
| | 11) CALCULATIONS FOR COMBUSTION AIR. |
| | SHOW COMBUSTION AIR FOR BOILER AND CALCS |
| | WATER HEATERS DIRECT VENT THRU ROOF NOT |
| | SHOWN. |
| | 12) INDICATE DELIVERY PRESSURE. FPU |
| | DELIVERS 12" TO 14" WC - .5 PSI |
| | 13) SUBMIT DETAIL SHOWING THE TYPE, SIZE |
| | LOCATION, AND TERMINATION OF GAS VENTS. |
| | |
| | REVIEW BY PAUL SCHMITZ/KEN STEVENS |
| | (561) 659-8096 EXT. 8233/8377 |