Plan Review Notes
Plan Review Notes For Permit 01071485
Permit Number 01071485
Review Stop M
Sequence Number 2
Notes
Date Text
2001-08-06 00:00:00REVIEW FOR SMOKE CONTROL SYSTEM FOR
 ATRIUM
 ***************DENIED*******************
 1. PLEASE CLARIFY MAXIMUM ATRIUM HEIGHT
 AS WE HAVE TWO DIFFERENT STATEMENTS AS
 TO HEIGHT.
 2. PROVIDE SEQUENCE OF OPERATION FOR
 DOOR OPENINGS AND ATRIUM SMOKE CONTROL
 3. DURING THE ORIGINAL MEETING ON SMOKE
 CONTROL THE BUILDING OFFICIAL REQUESTED
 IF YOU WERE USING AN ALTERNATIVE METHOD
 TO THE SBC USE THE 10 FOOT ABOVE THE
 SECOND FLOOR NOT THE 6 FOOT AS SHOWN IN
 THE REPORT.
 4. ALL ELEVATIONS OPENING TO THE ATRIUM
 ARE NOT INDICATED AS REQUESTED IN THE
 FIRST SET OF COMMENTS. PROVIDE
 INFORMATION ON THE ELEVATIONS INVOLVED,
 I,E. AREAS SHOWN AS OPEN TO BEYOND BY
 BALLROOM CONCOURSE BETWEEN COLUMNS U
 AND K.
 5. ARE ALL RESTROMS, THE ADMINISTRATIVE
 ASSISTANT (1N-49), RECEPTION AREA
 (1N-50) AND ANY OTHER AREA NOT
 SEPARATED BY RATED WALLS INCLUDED IN
 THE ATRIUM SIZE CALCULATION?
 6. AS PART OF THE SEQUENCE OF OPERATION,
 PROVIDE INFORMATION ON ALL DEVICES THAT
 WILL INITIATE THE SMOKE CONTROL SYSTEM.
 7. INDICATE IN THE SEQUENCE OF OPERATION
 HOW THE DIFFERENT FANS AND DOORS IN THE
 DIFFERENT ZONES WILL OPERATE. WILL ALL
 DOORS OPEN AND ALL FANS COME ON AR ONLY
 THOSE IN EFFECTED AREAS?
 8.SHOW FIREMANS OVERRIDE PANEL AND
 EXPLAIN FUNCTION.
 9. ON SHEET M5.103 SEQUENCE OF OPERATION
 SAYS THAT OPERATOR WILL BE ABLE TO
 OVERRIDE THE SYSTEM AT ANY TIME. DEFINE
 OPERATOR IN THIS STATEMENT.
 10. IF FANS OPERATE PRIOR TO DOOR
 OPENING, PROVIDE INFORMATION ON DOOR
 PRESURE. PROVIDE MAXIMUM DOOR PULL
 PRESSURES FOR ALL EXIT DOORS NOT OPENED
 AS PART OF THE SMOKE CONTROL SYSTEM.