Plan Review Notes
Plan Review Notes For Permit 01071485
Permit Number 01071485
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-10-18 00:00:001) SOME MATH ERRORS STILL EXIST IN
 OCCUPANT LOAD CHARTS 1 & 2.
 2) DO THE WALLS IN SERVICE CORRIDOR
 2N-28 CREATE HARD BARRIERS FOR EXITING
 ONCE PERSONS LEAVE THE BALLROOMS VIA
 THE EXIT DOORS.
 3) EMERGENCY LIGHTS STILL NOT CLEARLY
 IDENTIFIED IN BALLROOMS AND EXHIBIT
 HALL.
 4) THE FINAL REPORT FOR SMOKE CONTROL,
 SMOKE EXHAUST IS NOT SIGNED AND SEALED.
 ALSO THE FINAL REPORT MUST BE SUBMITTED
 TO THE BUILDING OFFICIAL FOR HIS
 REVIEW AND APPROVAL UNDER SEPARATE
 COVER. PLEASE VERIFY THAT THE REPORT
 IS THE FINAL DRAFT AND READY FOR
 SUBMITTAL. A REVIEW OF THIS DOCUMENT
 SUGGESTS SOME CORRELATION ISSUES STILL
 EXIST.
 5) COULD NOT LOCATE EXIT # 14 ON PAGE
 A1-4.1.
 6) PLEASE CLEARLY IDENTIFY THAT ALL
 PRESCRIPTIVE CODE REQUIREMENTS HAVE BEEN
 MET FOR THE RAMP BEING USED FOR
 EXITING ADJACENT TO THE LOADING DOCK.
 7) CO2 EXTINGUISHERS NOTED ON PAGE
 FP1-1.1. PLEASE EXPLAIN.
 8) ARE THE DUAL ENCLOSED STAIRS SCISSSOR
 STAIRS OR DOUBLE STAIRS.
 9) WEST WALL NOT RATED ON PAGE A1-5.1
 10) PLEASE BE ADVISED THAT CERTAIN
 RESTRICTIONS APPLY TO THE USE OF WOOD
 IN THE FIRE LIMITS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910