| 2001-10-18 00:00:00 | 1) SOME MATH ERRORS STILL EXIST IN |
| | OCCUPANT LOAD CHARTS 1 & 2. |
| | 2) DO THE WALLS IN SERVICE CORRIDOR |
| | 2N-28 CREATE HARD BARRIERS FOR EXITING |
| | ONCE PERSONS LEAVE THE BALLROOMS VIA |
| | THE EXIT DOORS. |
| | 3) EMERGENCY LIGHTS STILL NOT CLEARLY |
| | IDENTIFIED IN BALLROOMS AND EXHIBIT |
| | HALL. |
| | 4) THE FINAL REPORT FOR SMOKE CONTROL, |
| | SMOKE EXHAUST IS NOT SIGNED AND SEALED. |
| | ALSO THE FINAL REPORT MUST BE SUBMITTED |
| | TO THE BUILDING OFFICIAL FOR HIS |
| | REVIEW AND APPROVAL UNDER SEPARATE |
| | COVER. PLEASE VERIFY THAT THE REPORT |
| | IS THE FINAL DRAFT AND READY FOR |
| | SUBMITTAL. A REVIEW OF THIS DOCUMENT |
| | SUGGESTS SOME CORRELATION ISSUES STILL |
| | EXIST. |
| | 5) COULD NOT LOCATE EXIT # 14 ON PAGE |
| | A1-4.1. |
| | 6) PLEASE CLEARLY IDENTIFY THAT ALL |
| | PRESCRIPTIVE CODE REQUIREMENTS HAVE BEEN |
| | MET FOR THE RAMP BEING USED FOR |
| | EXITING ADJACENT TO THE LOADING DOCK. |
| | 7) CO2 EXTINGUISHERS NOTED ON PAGE |
| | FP1-1.1. PLEASE EXPLAIN. |
| | 8) ARE THE DUAL ENCLOSED STAIRS SCISSSOR |
| | STAIRS OR DOUBLE STAIRS. |
| | 9) WEST WALL NOT RATED ON PAGE A1-5.1 |
| | 10) PLEASE BE ADVISED THAT CERTAIN |
| | RESTRICTIONS APPLY TO THE USE OF WOOD |
| | IN THE FIRE LIMITS. |
| | |
| | MIKE CARSILLO, CAPTAIN |
| | 659-8096,EXT.8497 |
| | 835-2910 |