| 2001-10-12 00:00:00 | ***************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT COLOR CODING |
| | OF FEEDERS ON E5.101 SHOWS CONDUCTORS |
| | FOR 277/480 AS BLK,RED,BLUE. PLEASE |
| | NOTE THAT PER LOCAL AMENDMENTS THE COLOR |
| | -S FOR 277/480 IS BR/PURPLE/YELLOW. |
| | PLEASE ASLO PLACE THIS NOTE ON EACH OF |
| | THE ONE-LINE DIAGRAMS. ART:215 |
| | NOTE FROM NOTE #5 ON FIRST REVIEW. |
| | |
| | 2)NOTE: PLEASE NOTE, OCP IS NOW SHOWN |
| | ON LINE DIAGRAM FOR FIRE PUMP AS 800A`S |
| | ON FPL LINE. PLEASE NOTE THAT OCP THAT |
| | IS SHOWN COMING FROM GENERATOR IS SHOWN |
| | AT 200A`S.? PLEASE SEE 430-150. PLEASE |
| | NOTE LOAD FROM NEC IS SHOWN AT 240A`S |
| | AND IS THERE ANY PF CONSIDERATION? |
| | PLEASE CLARIFY LOADS ON 200HP MOTOR. |
| | 3)NOTE: PLEASE CLARIFY THE LOCATION OF |
| | THE 800A OCP AND ATS SHOWN ON LINE DIA- |
| | -GRAM E5.103. PLEASE NOTE THAT ONLY |
| | CONTROL PANEL IS SHOWN IN FIRE PUMP ROOM |
| | AND ONLY THE TWO ATS`S FOR EMDP1 AND 2 |
| | IS SHOWN IN MAIN ELECTRICAL ROOM. |
| | |
| | 4)NOTE: PLEASE NOTE THAT FROM NOTE#3 |
| | FIRST REVIEW, A NOTE WAS PLACE ON E2.102 |
| | "ATS IN THIS ROOM FOR SHUTOFF" PLEASE |
| | CLARIFY NOTE ON PLANS SO THAT THE NOTE |
| | IS MORE SPECIFIC OF MEANS OF SHUT-OFF |
| | AND FOR WHAT? (GENERATOR) |
| | |
| | 5)NOTE: PLEASE NOTE THAT IF USING "SCALE |
| | ON E4.104, PLEASE NOTE THE CLEARENCE FOR |
| | MAINS ON GENERATOR/CONTROL PANEL DO NOT |
| | SEEM TO MEET 110-26A "CONDITION 2" |
| | PLEASE CLARIFY. |
| | |
| | PLEASE NOTE THAT NOTES # 1 AND #5 WERE |
| | ADDRESSED FULLY. |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL OR CALL FOR A MEETING IF |
| | DESIRED. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-659-8096 EXT 8372 |