2001-10-12 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT COLOR CODING
 OF FEEDERS ON E5.101 SHOWS CONDUCTORS
 FOR 277/480 AS BLK,RED,BLUE. PLEASE
 NOTE THAT PER LOCAL AMENDMENTS THE COLOR
 -S FOR 277/480 IS BR/PURPLE/YELLOW.
 PLEASE ASLO PLACE THIS NOTE ON EACH OF
 THE ONE-LINE DIAGRAMS. ART:215
 NOTE FROM NOTE #5 ON FIRST REVIEW.
  
 2)NOTE: PLEASE NOTE, OCP IS NOW SHOWN
 ON LINE DIAGRAM FOR FIRE PUMP AS 800A`S
 ON FPL LINE. PLEASE NOTE THAT OCP THAT
 IS SHOWN COMING FROM GENERATOR IS SHOWN
 AT 200A`S.? PLEASE SEE 430-150. PLEASE
 NOTE LOAD FROM NEC IS SHOWN AT 240A`S
 AND IS THERE ANY PF CONSIDERATION?
 PLEASE CLARIFY LOADS ON 200HP MOTOR.
 3)NOTE: PLEASE CLARIFY THE LOCATION OF
 THE 800A OCP AND ATS SHOWN ON LINE DIA-
 -GRAM E5.103. PLEASE NOTE THAT ONLY
 CONTROL PANEL IS SHOWN IN FIRE PUMP ROOM
 AND ONLY THE TWO ATS`S FOR EMDP1 AND 2
 IS SHOWN IN MAIN ELECTRICAL ROOM.
  
 4)NOTE: PLEASE NOTE THAT FROM NOTE#3
 FIRST REVIEW, A NOTE WAS PLACE ON E2.102
 "ATS IN THIS ROOM FOR SHUTOFF" PLEASE
 CLARIFY NOTE ON PLANS SO THAT THE NOTE
 IS MORE SPECIFIC OF MEANS OF SHUT-OFF
 AND FOR WHAT? (GENERATOR)
  
 5)NOTE: PLEASE NOTE THAT IF USING "SCALE
 ON E4.104, PLEASE NOTE THE CLEARENCE FOR
 MAINS ON GENERATOR/CONTROL PANEL DO NOT
 SEEM TO MEET 110-26A "CONDITION 2"
 PLEASE CLARIFY.
  
 PLEASE NOTE THAT NOTES # 1 AND #5 WERE
 ADDRESSED FULLY.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL OR CALL FOR A MEETING IF
 DESIRED.
  