| Plan Review Notes For Permit 01071485 |
| Permit Number |
01071485 |
|
| Review Stop |
E |
| Sequence Number |
13 |
|
| Notes |
| Date |
Text |
| 2002-11-25 00:00:00 | REVISIONS, LTG CONTROLS#4 &5 | | | | | | ********** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE, LOADS SHOWN FOR | | | REVISED PANELS/RISERS NEED TO CORRELATE. | | | PLEASE NOTE WHEN LOAD CHANGES FOR "HP" | | | PANELS, PLEASE ADJUST FOR DPH`S THAT | | | FEED THOSE PANELS. | | | PLEASE ALSO NOTE, LOADS ON MSB-1 NEED TO | | | CORRELATE WITH DPH`S LOADS SHOWN. | | | PLEASE NOTE SOME DO AND SOME DON'T. | | | | | | PLEASE NOTE,LOADS ON MSB-2 AND | | | EMDP-1 NEED TO CORRELATE ALSO WITH | | | OTHER PANELS AND LOADS THEY SHOW. | | | | | | PLEASE SUBMIT THE ABOVE INFROAMTION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|