2001-08-05 00:00:00PLUMBING PLAN REVIEW, DENIED.
 CODE REFEREMCES,SBC-97,SGC-97 SPC-94
 FL ACCESSIBILIY CODE REVISED-98
 VOLUME (I)
 (1) FOOD SERVICE ESTABLISHMENTS,REQUIRE
 PLAN REVIEW/WITH COMMENTS PRIOR TO PLBG
 PLAN REVIEW,CONTACT DEPARTMENT OF HOTEL
 BUSINESS REGULATION, 954-958-5520.
 (2) GREASE TRAP,TYPE AND SIZE. CONTACT
 W PALM BCH RSTP,ENVIROMENTAL COMPLIANCE.
 RODNEY COMPO 561-837-4074 ORD# 2938-96.
 (3) SHT A1-7.1-7.2, PROVIDE CALCULATIONS
 FOR THE PRIMARY & SECONDARY STORM DRAINS
 SEC 1108.1,2,3,4,5,ONE HALF THE AREA OF
 VERTICAL WALLS, UPPER ROOFS DRAINING TO
 LOWER ROOFS, TO BE INCLUDED.
 (4) SHT A5-8.3 DETAIL #20, H/C,W/C FLUSH
 HANDLES TO COMPLY W/SEC 4.16.5, SHALL
 BE ON THE MOUNTING SIDE OF FIXTURE.
 (5)SHT D1-0.0,2.1 FINISH LEGEND,UNGLAZED
 FLOOR TILE, T-2,T-4,T-5,COMPLY W/SBC-97
 1204.2,NON ABSORBENT FLOOR SURFACE.
 VOLUME (II)
 (6) SHT INDEX: MINIMUM FACILITIES, SHOW
 NUMBER OF DRINKING FOUNTAINS,USE,TAB 407
 AND FACBC-98 REV,SEC 4.1.3 (A)(B).
 VOLUME (III) & (IV)
 (7) SHT P4-1.1 AHU CONDENSATE DRAIN DE-
 TAIL, COMPLY W/SEC 104.3 PLANS & SPEC'S,
 PROVIDE A ISOMETRIC DRAWING OF A COMMON
 A/C CONDENSATE SYSTEM,CONNECTED TO STORM
 DRAINAGE SYSTEM OUTSIDE OF BUILDING WITH
 A RELIEF VENT 6" ABOVE GRADE.
 (8) SHT P1-1.1, WATER HAMMER ARRETORS,TO
 BE INSTALLED AS PER MFG. INSTALLATION
 INSTRUCTIONS FOR SIZE AND PLACEMENT.
 SEC 607.8.2, INSTALLED AS PER PDI-WH201
 (9) SHT P2-1.1 COMPLY W/SEC 714 MAXIMUM
 FIXTURE LOAD ON THE DWV SYSTEM. SHOW
 FIXTURE UNIT LOAD THRU OUT SYSTEM.
 (10) SHT P4-2.2,2.4, CAN WASH AND TRASH
 COMPACTOR, CONNECT TO GREASE WASTE.
 LOCAL ORDINANCE # 2938-96.
 (11) SHT P4-2.1,2.3, STACK "D","Q",
 PLBG FIXTURES FROM UPPER FLOORS, SHALL
 NOT DISCHARGE INTO A BATTERY VENTED
 BRANCH SPC-95 SEC 914.1
 (12) SHT P4-1.1 EWH DETAIL,TO BE READILY
 ACCESSIBLE,SEC 501.7, PROVIDE A DETAIL
 OF A WORKING PLATFORM W/ A SHIPS LADDER,
 OR SET THE DWH THE ON FLOOR.
 SEC 507.8.2, MIN.SIZE PAN DRAIN, 1".
 DWH DRAINS,SEC 802,ALL I/D WASTE TO F/S.
 (13) SHT P3-1.5 ALCOVE DWV SYSTEM DESIGN
 COMLPY WITH 921.1, COMBINATION WASTE AND
 VENT SYSTEM. THIS SHOULD BE TYPICAL FOR
 CONSESSION AND FOODN SERVICE SYSTEMS.
 (14) SHT P4-2.1 THRU 2.4,STACK DIAGRAMS.
 CIRCUIT AND LOOP, BRANCH SOIL OR WASTE
 PIPE SHALL BE UNIFORM THROUGH ITS ENTIRE
 LENGTH. SEC 914.1
 (15A) SHT P2-1.1 TO 1.8, EXHIBIT HALL
 U/G DWV SYSTEM PIPING,TO COMPLY WITH SEC
 921, COMBINATION WASTE AND VENT SYSTEM.
 ONE VENT UPSTREAM, BETWEEN THE LAST TWO
 FIXTURE DRAINS, ONE VENT DOWN STREAM,
 BEFORE THE FIRST FIXTURE DRAIN.
 SEE ILLUSTRATION APPEX "J" PG.275,ALSO
 SEE DIFINITIONS CH-2 FIXTURE DRAIN AND
 FIXTURE BRANCH.
 (15B) PROVIDE SHOP DRAWINGS FOR THE U/G
 UTILITY SERVICE BOX,FROM THE MANUFACTURE
 TO SHOW HOW THERE IS NOT A CROSS CONNECT
 ION OF WASTE AND POTABLE WATER,SEC 601.5
 (16)SHT P2-1.1 THRU 4.1, SEC 104.3 PLANS
 PROVIDE ISOMETRIC DRAWINGS OF THE WATER
 PIPING SYSTEM, WITH CALCULATIONS FOR THE
 DISCHARGE FIXTURE UNIT DEMAND.
 NO MORE THAN TWO FIXTURES 0N 1/2" C/W.
 NO MORE THAN FOUR FIXTURES ON 1/2" H/W.
 MODEL CNTY WIDE AMENDMENTS, SPC-94,607.7
  
 GAS PERMITREQUIRMENTS
 CODE REFERENCES SGC-97,NFPA-54
 (17A) SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE,
 CORRESPONDING LENGTHS AND PIPE SIZES.
 (B) TYPE OF PIPING MATERIAL, ALL PIPE
 SIZES, TYPE OF GAS, BTU LOAD OF EACH
 APPLIANCE AND TOTAL BTU LOAD ON SYSTEM.
 (C) SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY,TO THE MOST REMOTE OUTLET IN
 THE BUILDING. (TOTAL DEVELOPED LGTH)
 (D) CALCULATIONS FOR COMBUSTION AIR
 (E) INDICATE DELIVERY PSI, (2# OR .5#).
 (F) SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE, TERMINATION OF GAS VENTS
 (G) SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT,TO VERIFY COMPLIANCE WITH
 LOCAL CODES.
 (H) SHOW LOCATION OF GAS METER.
 (I) SPECIFY, SIZE & TYPE OF REGULATORS.
 REQUIRED FOR THIS SYSTEM.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096 X 8233