| 2001-08-05 00:00:00 | PLUMBING PLAN REVIEW, DENIED. |
| | CODE REFEREMCES,SBC-97,SGC-97 SPC-94 |
| | FL ACCESSIBILIY CODE REVISED-98 |
| | VOLUME (I) |
| | (1) FOOD SERVICE ESTABLISHMENTS,REQUIRE |
| | PLAN REVIEW/WITH COMMENTS PRIOR TO PLBG |
| | PLAN REVIEW,CONTACT DEPARTMENT OF HOTEL |
| | BUSINESS REGULATION, 954-958-5520. |
| | (2) GREASE TRAP,TYPE AND SIZE. CONTACT |
| | W PALM BCH RSTP,ENVIROMENTAL COMPLIANCE. |
| | RODNEY COMPO 561-837-4074 ORD# 2938-96. |
| | (3) SHT A1-7.1-7.2, PROVIDE CALCULATIONS |
| | FOR THE PRIMARY & SECONDARY STORM DRAINS |
| | SEC 1108.1,2,3,4,5,ONE HALF THE AREA OF |
| | VERTICAL WALLS, UPPER ROOFS DRAINING TO |
| | LOWER ROOFS, TO BE INCLUDED. |
| | (4) SHT A5-8.3 DETAIL #20, H/C,W/C FLUSH |
| | HANDLES TO COMPLY W/SEC 4.16.5, SHALL |
| | BE ON THE MOUNTING SIDE OF FIXTURE. |
| | (5)SHT D1-0.0,2.1 FINISH LEGEND,UNGLAZED |
| | FLOOR TILE, T-2,T-4,T-5,COMPLY W/SBC-97 |
| | 1204.2,NON ABSORBENT FLOOR SURFACE. |
| | VOLUME (II) |
| | (6) SHT INDEX: MINIMUM FACILITIES, SHOW |
| | NUMBER OF DRINKING FOUNTAINS,USE,TAB 407 |
| | AND FACBC-98 REV,SEC 4.1.3 (A)(B). |
| | VOLUME (III) & (IV) |
| | (7) SHT P4-1.1 AHU CONDENSATE DRAIN DE- |
| | TAIL, COMPLY W/SEC 104.3 PLANS & SPEC'S, |
| | PROVIDE A ISOMETRIC DRAWING OF A COMMON |
| | A/C CONDENSATE SYSTEM,CONNECTED TO STORM |
| | DRAINAGE SYSTEM OUTSIDE OF BUILDING WITH |
| | A RELIEF VENT 6" ABOVE GRADE. |
| | (8) SHT P1-1.1, WATER HAMMER ARRETORS,TO |
| | BE INSTALLED AS PER MFG. INSTALLATION |
| | INSTRUCTIONS FOR SIZE AND PLACEMENT. |
| | SEC 607.8.2, INSTALLED AS PER PDI-WH201 |
| | (9) SHT P2-1.1 COMPLY W/SEC 714 MAXIMUM |
| | FIXTURE LOAD ON THE DWV SYSTEM. SHOW |
| | FIXTURE UNIT LOAD THRU OUT SYSTEM. |
| | (10) SHT P4-2.2,2.4, CAN WASH AND TRASH |
| | COMPACTOR, CONNECT TO GREASE WASTE. |
| | LOCAL ORDINANCE # 2938-96. |
| | (11) SHT P4-2.1,2.3, STACK "D","Q", |
| | PLBG FIXTURES FROM UPPER FLOORS, SHALL |
| | NOT DISCHARGE INTO A BATTERY VENTED |
| | BRANCH SPC-95 SEC 914.1 |
| | (12) SHT P4-1.1 EWH DETAIL,TO BE READILY |
| | ACCESSIBLE,SEC 501.7, PROVIDE A DETAIL |
| | OF A WORKING PLATFORM W/ A SHIPS LADDER, |
| | OR SET THE DWH THE ON FLOOR. |
| | SEC 507.8.2, MIN.SIZE PAN DRAIN, 1". |
| | DWH DRAINS,SEC 802,ALL I/D WASTE TO F/S. |
| | (13) SHT P3-1.5 ALCOVE DWV SYSTEM DESIGN |
| | COMLPY WITH 921.1, COMBINATION WASTE AND |
| | VENT SYSTEM. THIS SHOULD BE TYPICAL FOR |
| | CONSESSION AND FOODN SERVICE SYSTEMS. |
| | (14) SHT P4-2.1 THRU 2.4,STACK DIAGRAMS. |
| | CIRCUIT AND LOOP, BRANCH SOIL OR WASTE |
| | PIPE SHALL BE UNIFORM THROUGH ITS ENTIRE |
| | LENGTH. SEC 914.1 |
| | (15A) SHT P2-1.1 TO 1.8, EXHIBIT HALL |
| | U/G DWV SYSTEM PIPING,TO COMPLY WITH SEC |
| | 921, COMBINATION WASTE AND VENT SYSTEM. |
| | ONE VENT UPSTREAM, BETWEEN THE LAST TWO |
| | FIXTURE DRAINS, ONE VENT DOWN STREAM, |
| | BEFORE THE FIRST FIXTURE DRAIN. |
| | SEE ILLUSTRATION APPEX "J" PG.275,ALSO |
| | SEE DIFINITIONS CH-2 FIXTURE DRAIN AND |
| | FIXTURE BRANCH. |
| | (15B) PROVIDE SHOP DRAWINGS FOR THE U/G |
| | UTILITY SERVICE BOX,FROM THE MANUFACTURE |
| | TO SHOW HOW THERE IS NOT A CROSS CONNECT |
| | ION OF WASTE AND POTABLE WATER,SEC 601.5 |
| | (16)SHT P2-1.1 THRU 4.1, SEC 104.3 PLANS |
| | PROVIDE ISOMETRIC DRAWINGS OF THE WATER |
| | PIPING SYSTEM, WITH CALCULATIONS FOR THE |
| | DISCHARGE FIXTURE UNIT DEMAND. |
| | NO MORE THAN TWO FIXTURES 0N 1/2" C/W. |
| | NO MORE THAN FOUR FIXTURES ON 1/2" H/W. |
| | MODEL CNTY WIDE AMENDMENTS, SPC-94,607.7 |
| | |
| | GAS PERMITREQUIRMENTS |
| | CODE REFERENCES SGC-97,NFPA-54 |
| | (17A) SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE, |
| | CORRESPONDING LENGTHS AND PIPE SIZES. |
| | (B) TYPE OF PIPING MATERIAL, ALL PIPE |
| | SIZES, TYPE OF GAS, BTU LOAD OF EACH |
| | APPLIANCE AND TOTAL BTU LOAD ON SYSTEM. |
| | (C) SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY,TO THE MOST REMOTE OUTLET IN |
| | THE BUILDING. (TOTAL DEVELOPED LGTH) |
| | (D) CALCULATIONS FOR COMBUSTION AIR |
| | (E) INDICATE DELIVERY PSI, (2# OR .5#). |
| | (F) SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE, TERMINATION OF GAS VENTS |
| | (G) SUBMIT MANUFACTURE SHEETS FOR ALL |
| | GAS EQUIPMENT,TO VERIFY COMPLIANCE WITH |
| | LOCAL CODES. |
| | (H) SHOW LOCATION OF GAS METER. |
| | (I) SPECIFY, SIZE & TYPE OF REGULATORS. |
| | REQUIRED FOR THIS SYSTEM. |
| | END OF COMMENTSPAUL SCHMITZ |