Plan Review Notes
Plan Review Notes For Permit 01071485
Permit Number 01071485
Review Stop M
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:00**************DENIED********************
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS
 PRIOR TO RESUBMITTAL OF PLANS.
 1.THE DUCT BANK DETAIL SHOWN ON A1-17
 SHOWS DUCT ON COMPACTED EARTH. !997 SMC
 607 REQUIRES MECHANICAL DUCT TO BE
 ENCLASED ON ALL SIDES WITH NOT LESS
 THAN 2" OF CONCRETE.
 2. THE LOUVER OPENING FOR GENERATOR ROOM
 SHOWN ON A2-1.3 ARE REQUIRED TO BE
 PROTECTED BY APPROVED FIRE DAMPERS TO
 MAINTAIN THE RATING OF THIS ROOM.
 PROVIDE INFORMATION ON OPENING
 PROTECTION.
 3. DOES THE PROJECTION EQUIPMENT SHOWN
 ON A3-1.6 REQUIRE ADDITIONAL
 VENTILATION OR EXHAUST? PROVIDE
 MANUFACTURES RECOMMENDATIONS ON
 EQUIPMENT REQUIREMENTS.
 4. OVERHEAD DOORS SHOWN IN RATED WALLS
 WILL BE REQUIRED TO HAVE AUTOMATIC
 CLOSURE ABILITY TO PROTECT OPENING.
 PROVIDE INFORMATION ON DOOR FUNCTION TO
 COMPLY WITH REQUIREMENTS FOR OPENING
 PROTECTION.
 5. PLAN SHOWS VEHICLE ACCESS TO SECOND
 FLOOR. WHAT REQUIREMENTS FOR ADDITONA
 OUTSIDE AIR OR MONITORING FOR CARBON
 MONOXIDE DOES THIS ADD TO THE FACILITY?
 PROVIDE CALCULATIONS SHOWING WORST CASE
 LOAD OF VEHICLES.
 6. NO INFORMATION WAS SHOWN FOR DISPOSAL
 OF CONDENSATE FROM AIR HANDLING
 EQUIPMENT. PROVIDE LOCATION AND SIZES
 OF THIS PIPING AND DISPOSAL LOCATION.
 NOTE: LOCAL ORDINACE DOES NOT PERMIT
 CONDENSATE TO GO TO THE SANITARY SYSTEM.
 7. CHILLER SPECS ON M 0.002 SHOW
 EFFIENCY RATING AS NLPV. FLORIDA ENERGY
 CODE REQUIRES RATING IN ILPV. PLEASE
 PROVIDE CHILLER RATING AS ILPV NUMBER
 COMPLYING WITH TABLE 4-5 MINIMUM
 PERFORMANCE EFFICIENCIES.
 8. ENERGY CALCS SHOW 4 SYSTEMS WITH
 VARIOUS EFFICIENCIES. NOT ALL EQUIPMENT
 APPEARS TO BE LISTED IN CALCS PROVIDED.
 SHOW ALL EQUIPMENT TO BE INSTALLED OR
 SUMMARY AS PROVIDED FOR IN FLA ENERGY
 CODE,
 9. M0.002 AIR BALANCE EXHAUST AND
 OUTSIDE AIR VALUES DO NOT ADD UP TO
 EQUIPMENT VALUES SHOWN. PROVIDE AIR
 BALANCE SCHEDULE SHOWING COMPLIANCE
 WITH 1997 SMC 501.2 AND OUTSIDE AIR
 CALCULATIONS SHOWING COMPLIANCE WITH
 ASHRAE 62.89.
 10. OUTSIDE AIR REQUIRED FOR TICKET
 OFFICE NEEDS TO BE DUCTED TO THE RETURN
 AIR OF THE UNIT SERVING THIS SPACE FOR
 BALANCING PURPOSES
 11.WOMEN'S AND MEN'S BATHROOMS AND
 LOCKER ROOMS SHOWN ON M2.101 HAVE 1400
 CFM OF EXHAUST AIR AND ONLY 200 CFM OF
 SUPPLY AIR. ANOTHER AREA HAS 600 CFM
 EXHAUST AND 100 S/A. RM 1N23+ 24 HAVE
 3050 EXHAUST AIR AND 850 SUPPLY AIR.
 PROVIDE AIR BALANCE IN COMPLIANCE WITH
 1997 SMC 501.2
 12. NO RETURN AIR IS SHOWN IN SATELLITE
 ROOM 1N53 AND IN ROOM 1N-57 S/A IS 100
 CFM AND R/A IS 10CFM.
 13. ADMIN AREA (1N64 HAS 850CFM S/A AND
 920 CFM R/A AND RMS 1N59/60 HAS 530 CFM
 EXHAUST AIR AND 100 CFM S/A.
 14. NO RETURN AIR SHOWN FOR DOCK OFFICE
 1N-39 ANY AREA WITH 350 CFM OR MORE
 NEEDS RETURN FROM ROOM.
 15. MACHINE ROOM HAS 490 CFM OF EXHAUST
 AIR AND NO PROVISION FOR MAKE UP AIR.
 SHOW COMPLIANCE WITH SMC 501.2.
 16. NO FIRE DAMPERS SHOWN AT FLOOR
 PENETRATIONS OF DUCT ON M 2.104
 17. WOMEN'S ROOM 1C 17 AND 14 HAVE 670
 CFM OF EHAUST AND 310 CFM MAKE UP AIR
 INCLUDING U/C OF DOOR.
 18. ON M 2.106 NO FIRE DAMPERS SHOWN IN
 EAST WALL OF SHOW AMANGERS
 OFFICE(1N-68)AT DUCT PENETRATION.
 19. NO PROTECTION OF WALL PENETRATIONS
 SHOWN FOR TRANSFER GRILLS, DOOR GRILLS,
 AND OVERHEAD DOORS ON WEST SIDE OF
 SERVICE CORRIDOR RATED WALL BETWEEN
 COLUMN S AND T ON M2.107
 20. NO FIRE DAMPERS SHOWN IN RATED WALL
 AT COLUMN V DUCT PENETRATIONS CLOSE TO
 AREA 7 AND 8 MATCH LINE.
 21. M2.201 MEN,S ROOM 2N-15 HAS 740 CFM
 E/A AND 485CFM MAKE UP AIR INCLUDING
 DOOR GRILL. JANITOR'S CLOSET HAS 140
 CFM E/A AND 590 CFM MAKE UP(INTO MEN'S
 ROOM).
 22. SYMBOL FOR DUCT ELEVATION CHANGE
 DIFFERS FROM LEGEND TO WHATS USED ON
 DRAWINGS.
 23. NO COMBUSTIBLES ALLOWED IN RETURN
 AIR PLENUM AREAS.
 24. M2.201 CLARIFY WHICH WALL IS RATED
 AT ELEC AND TELE RMS 2N-12 AND 10. GAP
 ON HOURLY RATED WALL PLAN A1-5.2. DUCTS
 PENETRATE SOUTH WALL W/ NO FIRE DAMPERS
 SHOWN BY COLUMNS C.8 AND 4 AT 16X18"
 DUCT PENETRATION.
 25. M2.201 NO FIRE DAMPER SHOWN BY
 COLUMN J AND 4 AT 14" DUCT PENETRATION
 26. WOMEN'S BATH AND LOCKER ROOM ON
 M2.202 HAS 500 CFM TOTAL EXHAUST AND
 250 CFM OF MAKE UP AIR
 27. NO FIRE DAMPERS SHOWN ALONG RATED
 SERVICE CORRIDOR 2N-28 X 10 PLACES ON
 M2.202. DOOR GRILLS ARE NOT SHOWN AS
 RATED. FLOOR CEILING PENETRATIONS TO BE
 PROTECTED BY 1997 SMC 610.
 28. M2.203 AND 4 NO FIRE DAMPERS
 INDICATED AT STAIR 8 RATED WALL 10X16
 DUCT PENETRATION COLUMN C.7.
 ARE MECH ROOM 2W-15, 2W-16 AND 2W-18
 WALLS RATED? PLAN SHOWS DASHED LINES
 BUT NO FIRE DAMPERS AT DUCT
 PENETRATIONS.
 29. M 2.207 ELECTRIC ROOM 2E-16 HAS 575
 CFM OF SUPPLY AIR BUT NO RETURN AIR PATH
 FROM ROOM. PROVIDE RETURN AIR PER SMC
 501.2
 30. M2.207 NO FIRE DAMPERS SHOWN AT
 RATED WALL DUCT PENETRATION 18X20 DUCT
 BY COLUMN 16 18X20 DUCT COLUMN 15 AND
 10X6 DUCT COLUMN T
 31. M2.208 NO FIRE DAMPERS SHOWN AT 6X6
 DUCT INTO STORAGE ROOM 2E-30 RATED WALL
 PENETRATION.
 32. M3.201 NO FIRE DAMPER SHOWN AT 10X6
 DUCT AND 18X20 DUCT INTO MECH ROOM.
 33. M3.202 SHOW FIRE DAMPERS AT DUCT
 PENETRATIONS IF WALLS ARE RATED.
 34. PROVIDE INFORMATION ON TYPE AND
 QUANTITY OF REFRIGERANT PER CHILLER.
 TYPE DETERMINES SETPOINT FOR
 REFRIGERANT LEAK DETECTION SYSTEM.
 35. M5.104 OUTSIDE AIR REQUIRED BY
 ASHRAE 62.89 SHALL NOT BE REDUCED BY
 CO2 SENSORS. PROVIDE INFORMATION ON
 FUNCTION OF CO2 SENSOR.
 36.DUCT SMOKE DETECTOR IN RETURN AIR
 SHALL BE PRIOR TO ANY MIXINF OF OUTSIDE
 AIR.
 37. NOTE DO NOT RUN AIR CONDITIONING
 EQUIPMENT UNTIL CONSTRUCTION IS
 FINISHED AND CITY MECHANICAL INSPECTOR
 APPROVAL IS GIVEN.
 38. MAINTAIN CLEANLINESS OF DUCT DURING
 CONSTRUCTION.
 39. CONDENSATE DRAIN LINES ARE NOT
 SHOWN.
 40. FIRE DAMPERS WILL BE REQUIRED TO
 MAINTAIN RATING OF VAULT ROOM THREE
 HOUR WALLS.
 41. CONDENSING EQUIPMENT FOR
 COOLERS/FREEZERS SHALL NOT BE IN THE
 COOL AIR STREAM OF ANOTHER UNIT. ENERGY
 EFFICIENCY REQUIREMENTS FOR FLORIDA
 407.1
 42. EXHAUST WILL BE REQUIRED IN AREA OF
 MOP SINKS SHOWN ON FS 2.1 C-32
 CONCESSION PER 1997 SMC 501.4
 THIS DOES NOT INCLUDE REVIEW COMMENTS
 FOR THE ATRIUM SMOKE CONTROL SYSTEM.
 43. CLEARLY INDICATE IF THE DAMPER IS A
 SMOKE FIRE DAMPER, FIRE DAMPER OR SMOKE
 DAMPER ON THE PLAN. THE LOCATION OF ALL
 REQUIRED DAMPERS ARE REQUIRED TO BE
 CLEARLY INDICATED ON THE PLAN BY THE
 DESIGNER BY 1997 610.6.
 44. FLOOR DRAINS INDICATED FOR THE
 CHILLER PLANT WILL NOT BE PERMITTED IF
 THEY WOULD ALLOW FOR THE SPREAD OF
 REFRIGERANT LEAK FROM ONE PART OF THE
 BUILDING TO ANOTHER.
 45. CLEARLY INDICATE ON PLAN THE
 LOCATION OF THE CHILLERS RELIEF PIPE
 TERMINATION SHOWING COMPLIANCE WITH
 1997 SMC 1105.9
 46. HORN AND STROBE FOR CHILLER ROOM
 REFRIGERANT LEAK DETECTORS SHALL BE
 LOCATED INSIDE AND OUTSIDE THE ROOM
 INAREAS WHERE THEY CAN BE SEEN AND
 HEARD.
 47. THE BREATHING APPERATUR REQUIRED
 WILL NEED TO BE LOCATED OUTSIDE OF THE
 CHILLER ROOM.
 48. THE SINGLE DOOR AT THE BACK OF THE
 CHILLER ROOM NEEDS TO HAVE SIGNS
 PROHIBITING ACCESS IN CASE OF A LEAK
 AND EXPLAINING THE DESIRED PROCEDURE.
 49. SIGNS AS REQUIRED BY SMC CH 11 AND
 ASHREA 15 WILL BE REQUIRED.
 50 ACCEPTANCE OF THE REFRIGERANT LEAK
 DETECTION WILL NEED TO BE BY TEST IN
 THE PRESENCE OF THE MECHANICAL
 INSPECTOR AND THE FIRE INSPECTOR,PRIOR
 TO LOADING OF REFIGERANT INTO THE
 CHILLERS OR IF THE CHILLERS ARE SHIPPED
 LOADED, PRIOR TO START UP.
 51. ROOF PLAN SHOWS A SF AND EF
 TOGETHER. WHAT TYPE EQUIPMENT IS THIS
 AND HOW DOES IT COMPLY WITH THE CODE
 REQUIRED TEN FOOT SEPARATION FROM EACH
 OTHER.
 52. WHAT IS THE FUNCTION OF SEF 8? IT
 APPEARS TO BE IN THE AREA OF THE
 SERVICE CORRIDOR, WHICH DOES NOT APPEAR
 TO BE PART OF THE ATRIUM.