| 2001-08-02 00:00:00 | **************DENIED******************** |
| | |
| | PLEASE ADDRESS THE FOLLOWING COMMENTS |
| | PRIOR TO RESUBMITTAL OF PLANS. |
| | 1.THE DUCT BANK DETAIL SHOWN ON A1-17 |
| | SHOWS DUCT ON COMPACTED EARTH. !997 SMC |
| | 607 REQUIRES MECHANICAL DUCT TO BE |
| | ENCLASED ON ALL SIDES WITH NOT LESS |
| | THAN 2" OF CONCRETE. |
| | 2. THE LOUVER OPENING FOR GENERATOR ROOM |
| | SHOWN ON A2-1.3 ARE REQUIRED TO BE |
| | PROTECTED BY APPROVED FIRE DAMPERS TO |
| | MAINTAIN THE RATING OF THIS ROOM. |
| | PROVIDE INFORMATION ON OPENING |
| | PROTECTION. |
| | 3. DOES THE PROJECTION EQUIPMENT SHOWN |
| | ON A3-1.6 REQUIRE ADDITIONAL |
| | VENTILATION OR EXHAUST? PROVIDE |
| | MANUFACTURES RECOMMENDATIONS ON |
| | EQUIPMENT REQUIREMENTS. |
| | 4. OVERHEAD DOORS SHOWN IN RATED WALLS |
| | WILL BE REQUIRED TO HAVE AUTOMATIC |
| | CLOSURE ABILITY TO PROTECT OPENING. |
| | PROVIDE INFORMATION ON DOOR FUNCTION TO |
| | COMPLY WITH REQUIREMENTS FOR OPENING |
| | PROTECTION. |
| | 5. PLAN SHOWS VEHICLE ACCESS TO SECOND |
| | FLOOR. WHAT REQUIREMENTS FOR ADDITONA |
| | OUTSIDE AIR OR MONITORING FOR CARBON |
| | MONOXIDE DOES THIS ADD TO THE FACILITY? |
| | PROVIDE CALCULATIONS SHOWING WORST CASE |
| | LOAD OF VEHICLES. |
| | 6. NO INFORMATION WAS SHOWN FOR DISPOSAL |
| | OF CONDENSATE FROM AIR HANDLING |
| | EQUIPMENT. PROVIDE LOCATION AND SIZES |
| | OF THIS PIPING AND DISPOSAL LOCATION. |
| | NOTE: LOCAL ORDINACE DOES NOT PERMIT |
| | CONDENSATE TO GO TO THE SANITARY SYSTEM. |
| | 7. CHILLER SPECS ON M 0.002 SHOW |
| | EFFIENCY RATING AS NLPV. FLORIDA ENERGY |
| | CODE REQUIRES RATING IN ILPV. PLEASE |
| | PROVIDE CHILLER RATING AS ILPV NUMBER |
| | COMPLYING WITH TABLE 4-5 MINIMUM |
| | PERFORMANCE EFFICIENCIES. |
| | 8. ENERGY CALCS SHOW 4 SYSTEMS WITH |
| | VARIOUS EFFICIENCIES. NOT ALL EQUIPMENT |
| | APPEARS TO BE LISTED IN CALCS PROVIDED. |
| | SHOW ALL EQUIPMENT TO BE INSTALLED OR |
| | SUMMARY AS PROVIDED FOR IN FLA ENERGY |
| | CODE, |
| | 9. M0.002 AIR BALANCE EXHAUST AND |
| | OUTSIDE AIR VALUES DO NOT ADD UP TO |
| | EQUIPMENT VALUES SHOWN. PROVIDE AIR |
| | BALANCE SCHEDULE SHOWING COMPLIANCE |
| | WITH 1997 SMC 501.2 AND OUTSIDE AIR |
| | CALCULATIONS SHOWING COMPLIANCE WITH |
| | ASHRAE 62.89. |
| | 10. OUTSIDE AIR REQUIRED FOR TICKET |
| | OFFICE NEEDS TO BE DUCTED TO THE RETURN |
| | AIR OF THE UNIT SERVING THIS SPACE FOR |
| | BALANCING PURPOSES |
| | 11.WOMEN'S AND MEN'S BATHROOMS AND |
| | LOCKER ROOMS SHOWN ON M2.101 HAVE 1400 |
| | CFM OF EXHAUST AIR AND ONLY 200 CFM OF |
| | SUPPLY AIR. ANOTHER AREA HAS 600 CFM |
| | EXHAUST AND 100 S/A. RM 1N23+ 24 HAVE |
| | 3050 EXHAUST AIR AND 850 SUPPLY AIR. |
| | PROVIDE AIR BALANCE IN COMPLIANCE WITH |
| | 1997 SMC 501.2 |
| | 12. NO RETURN AIR IS SHOWN IN SATELLITE |
| | ROOM 1N53 AND IN ROOM 1N-57 S/A IS 100 |
| | CFM AND R/A IS 10CFM. |
| | 13. ADMIN AREA (1N64 HAS 850CFM S/A AND |
| | 920 CFM R/A AND RMS 1N59/60 HAS 530 CFM |
| | EXHAUST AIR AND 100 CFM S/A. |
| | 14. NO RETURN AIR SHOWN FOR DOCK OFFICE |
| | 1N-39 ANY AREA WITH 350 CFM OR MORE |
| | NEEDS RETURN FROM ROOM. |
| | 15. MACHINE ROOM HAS 490 CFM OF EXHAUST |
| | AIR AND NO PROVISION FOR MAKE UP AIR. |
| | SHOW COMPLIANCE WITH SMC 501.2. |
| | 16. NO FIRE DAMPERS SHOWN AT FLOOR |
| | PENETRATIONS OF DUCT ON M 2.104 |
| | 17. WOMEN'S ROOM 1C 17 AND 14 HAVE 670 |
| | CFM OF EHAUST AND 310 CFM MAKE UP AIR |
| | INCLUDING U/C OF DOOR. |
| | 18. ON M 2.106 NO FIRE DAMPERS SHOWN IN |
| | EAST WALL OF SHOW AMANGERS |
| | OFFICE(1N-68)AT DUCT PENETRATION. |
| | 19. NO PROTECTION OF WALL PENETRATIONS |
| | SHOWN FOR TRANSFER GRILLS, DOOR GRILLS, |
| | AND OVERHEAD DOORS ON WEST SIDE OF |
| | SERVICE CORRIDOR RATED WALL BETWEEN |
| | COLUMN S AND T ON M2.107 |
| | 20. NO FIRE DAMPERS SHOWN IN RATED WALL |
| | AT COLUMN V DUCT PENETRATIONS CLOSE TO |
| | AREA 7 AND 8 MATCH LINE. |
| | 21. M2.201 MEN,S ROOM 2N-15 HAS 740 CFM |
| | E/A AND 485CFM MAKE UP AIR INCLUDING |
| | DOOR GRILL. JANITOR'S CLOSET HAS 140 |
| | CFM E/A AND 590 CFM MAKE UP(INTO MEN'S |
| | ROOM). |
| | 22. SYMBOL FOR DUCT ELEVATION CHANGE |
| | DIFFERS FROM LEGEND TO WHATS USED ON |
| | DRAWINGS. |
| | 23. NO COMBUSTIBLES ALLOWED IN RETURN |
| | AIR PLENUM AREAS. |
| | 24. M2.201 CLARIFY WHICH WALL IS RATED |
| | AT ELEC AND TELE RMS 2N-12 AND 10. GAP |
| | ON HOURLY RATED WALL PLAN A1-5.2. DUCTS |
| | PENETRATE SOUTH WALL W/ NO FIRE DAMPERS |
| | SHOWN BY COLUMNS C.8 AND 4 AT 16X18" |
| | DUCT PENETRATION. |
| | 25. M2.201 NO FIRE DAMPER SHOWN BY |
| | COLUMN J AND 4 AT 14" DUCT PENETRATION |
| | 26. WOMEN'S BATH AND LOCKER ROOM ON |
| | M2.202 HAS 500 CFM TOTAL EXHAUST AND |
| | 250 CFM OF MAKE UP AIR |
| | 27. NO FIRE DAMPERS SHOWN ALONG RATED |
| | SERVICE CORRIDOR 2N-28 X 10 PLACES ON |
| | M2.202. DOOR GRILLS ARE NOT SHOWN AS |
| | RATED. FLOOR CEILING PENETRATIONS TO BE |
| | PROTECTED BY 1997 SMC 610. |
| | 28. M2.203 AND 4 NO FIRE DAMPERS |
| | INDICATED AT STAIR 8 RATED WALL 10X16 |
| | DUCT PENETRATION COLUMN C.7. |
| | ARE MECH ROOM 2W-15, 2W-16 AND 2W-18 |
| | WALLS RATED? PLAN SHOWS DASHED LINES |
| | BUT NO FIRE DAMPERS AT DUCT |
| | PENETRATIONS. |
| | 29. M 2.207 ELECTRIC ROOM 2E-16 HAS 575 |
| | CFM OF SUPPLY AIR BUT NO RETURN AIR PATH |
| | FROM ROOM. PROVIDE RETURN AIR PER SMC |
| | 501.2 |
| | 30. M2.207 NO FIRE DAMPERS SHOWN AT |
| | RATED WALL DUCT PENETRATION 18X20 DUCT |
| | BY COLUMN 16 18X20 DUCT COLUMN 15 AND |
| | 10X6 DUCT COLUMN T |
| | 31. M2.208 NO FIRE DAMPERS SHOWN AT 6X6 |
| | DUCT INTO STORAGE ROOM 2E-30 RATED WALL |
| | PENETRATION. |
| | 32. M3.201 NO FIRE DAMPER SHOWN AT 10X6 |
| | DUCT AND 18X20 DUCT INTO MECH ROOM. |
| | 33. M3.202 SHOW FIRE DAMPERS AT DUCT |
| | PENETRATIONS IF WALLS ARE RATED. |
| | 34. PROVIDE INFORMATION ON TYPE AND |
| | QUANTITY OF REFRIGERANT PER CHILLER. |
| | TYPE DETERMINES SETPOINT FOR |
| | REFRIGERANT LEAK DETECTION SYSTEM. |
| | 35. M5.104 OUTSIDE AIR REQUIRED BY |
| | ASHRAE 62.89 SHALL NOT BE REDUCED BY |
| | CO2 SENSORS. PROVIDE INFORMATION ON |
| | FUNCTION OF CO2 SENSOR. |
| | 36.DUCT SMOKE DETECTOR IN RETURN AIR |
| | SHALL BE PRIOR TO ANY MIXINF OF OUTSIDE |
| | AIR. |
| | 37. NOTE DO NOT RUN AIR CONDITIONING |
| | EQUIPMENT UNTIL CONSTRUCTION IS |
| | FINISHED AND CITY MECHANICAL INSPECTOR |
| | APPROVAL IS GIVEN. |
| | 38. MAINTAIN CLEANLINESS OF DUCT DURING |
| | CONSTRUCTION. |
| | 39. CONDENSATE DRAIN LINES ARE NOT |
| | SHOWN. |
| | 40. FIRE DAMPERS WILL BE REQUIRED TO |
| | MAINTAIN RATING OF VAULT ROOM THREE |
| | HOUR WALLS. |
| | 41. CONDENSING EQUIPMENT FOR |
| | COOLERS/FREEZERS SHALL NOT BE IN THE |
| | COOL AIR STREAM OF ANOTHER UNIT. ENERGY |
| | EFFICIENCY REQUIREMENTS FOR FLORIDA |
| | 407.1 |
| | 42. EXHAUST WILL BE REQUIRED IN AREA OF |
| | MOP SINKS SHOWN ON FS 2.1 C-32 |
| | CONCESSION PER 1997 SMC 501.4 |
| | THIS DOES NOT INCLUDE REVIEW COMMENTS |
| | FOR THE ATRIUM SMOKE CONTROL SYSTEM. |
| | 43. CLEARLY INDICATE IF THE DAMPER IS A |
| | SMOKE FIRE DAMPER, FIRE DAMPER OR SMOKE |
| | DAMPER ON THE PLAN. THE LOCATION OF ALL |
| | REQUIRED DAMPERS ARE REQUIRED TO BE |
| | CLEARLY INDICATED ON THE PLAN BY THE |
| | DESIGNER BY 1997 610.6. |
| | 44. FLOOR DRAINS INDICATED FOR THE |
| | CHILLER PLANT WILL NOT BE PERMITTED IF |
| | THEY WOULD ALLOW FOR THE SPREAD OF |
| | REFRIGERANT LEAK FROM ONE PART OF THE |
| | BUILDING TO ANOTHER. |
| | 45. CLEARLY INDICATE ON PLAN THE |
| | LOCATION OF THE CHILLERS RELIEF PIPE |
| | TERMINATION SHOWING COMPLIANCE WITH |
| | 1997 SMC 1105.9 |
| | 46. HORN AND STROBE FOR CHILLER ROOM |
| | REFRIGERANT LEAK DETECTORS SHALL BE |
| | LOCATED INSIDE AND OUTSIDE THE ROOM |
| | INAREAS WHERE THEY CAN BE SEEN AND |
| | HEARD. |
| | 47. THE BREATHING APPERATUR REQUIRED |
| | WILL NEED TO BE LOCATED OUTSIDE OF THE |
| | CHILLER ROOM. |
| | 48. THE SINGLE DOOR AT THE BACK OF THE |
| | CHILLER ROOM NEEDS TO HAVE SIGNS |
| | PROHIBITING ACCESS IN CASE OF A LEAK |
| | AND EXPLAINING THE DESIRED PROCEDURE. |
| | 49. SIGNS AS REQUIRED BY SMC CH 11 AND |
| | ASHREA 15 WILL BE REQUIRED. |
| | 50 ACCEPTANCE OF THE REFRIGERANT LEAK |
| | DETECTION WILL NEED TO BE BY TEST IN |
| | THE PRESENCE OF THE MECHANICAL |
| | INSPECTOR AND THE FIRE INSPECTOR,PRIOR |
| | TO LOADING OF REFIGERANT INTO THE |
| | CHILLERS OR IF THE CHILLERS ARE SHIPPED |
| | LOADED, PRIOR TO START UP. |
| | 51. ROOF PLAN SHOWS A SF AND EF |
| | TOGETHER. WHAT TYPE EQUIPMENT IS THIS |
| | AND HOW DOES IT COMPLY WITH THE CODE |
| | REQUIRED TEN FOOT SEPARATION FROM EACH |
| | OTHER. |
| | 52. WHAT IS THE FUNCTION OF SEF 8? IT |
| | APPEARS TO BE IN THE AREA OF THE |
| | SERVICE CORRIDOR, WHICH DOES NOT APPEAR |
| | TO BE PART OF THE ATRIUM. |