| 2001-08-10 00:00:00 | 1) PLEASE BE ADVISED THAT THIS BUILDING |
| | IS LOCATED WITHIN THE CITY FIRE LIMITS. |
| | CERTAIN RESTRICTIONS APPLY. |
| | 2) PLEASE BE ADVISED THAT CITY CODE |
| | SECTION 11-73 PROHIBITS THE USE OF |
| | OPEN FLAME DEVICES IN PUBLIC ASSEMBLY |
| | OCCUPANCIES. |
| | 3) PLEASE INDICATE COMPLIANCE WITH |
| | PRESCRIPTIVE CODE REQUIREMENTS OF NFPA |
| | 101, 2000 EDITION. |
| | 4) STILL HAVE NOT RECEIVED LETTER |
| | REGARDING THE NON USE OF PYROTECHNICS |
| | WITHIN THE BUILDING. |
| | 5) FIRE HYDRANTS NOT SHOWN ON SITE PLAN. |
| | ADDITIONAL FIRE HYDRANTS HAVE BEEN |
| | AGREED TO BY THE DESIGN TEAM. |
| | 6) OCCUPANT LOAD CHART, LEVEL ONE ON |
| | PAGE A1-4.1 IS NOT CORRECT. MATH ERRORS |
| | EXIST. |
| | 7) OCCUPANT LOAD CHART FOR LEVEL TWO |
| | HAS THE SAME PROBLEM. |
| | 8) VOID SPACE UNDERNEATH MONUMENTAL |
| | STAIR ON PAGE A2-1.1, CONFIRM USE IF |
| | ANY. |
| | 9) PLEASE EXPLAIN USE FOR OVERHEAD DOORS |
| | IN RATED FIRE WALLS. WHEN OPENED HOW |
| | DO THESE DOORS CLOSE AUTOMATICALLY. |
| | ARE SMOKE DETECTORS TIED INTO THESE |
| | DOORS. PRODUCT APPROVALS NEEDED FOR ALL |
| | OVERHEAD FIRE DOORS. DOWN ON ALL ALARMS. |
| | 10) PLEASE EXPLAIN OPPOSING DOORS NEAR |
| | CHILLER PLANT. |
| | 11) PLEASE EXPLAIN USE OF PANTRY. |
| | 12) EXPLAIN 16'-0 HIGH SLIDING METAL |
| | DOORS. HOW DO THEY SLIDE WITHOUT |
| | INTERFERING WITH DOORS USED FOR |
| | EXITING. |
| | 13) HOW DOES THE 30' HIGH OPERABLE |
| | PARTITION WALL WORK. |
| | 14) PLEASE EXPLAIN ONE HOUR RATED |
| | CONTINOUSLY HINGED OPERABLE WALL, |
| | MEETING ROOM 1E-13. |
| | 15) FRT PLYWOOD TO 6'-0 AFFF IN SERVICE |
| | CORRIDOR 2N-28 IS USED FOR WHAT. |
| | 16) PROPOSED FURNITURE LAYOUT IN |
| | PRE-FUNCTION AREAS SHOULD BE SHOWN. |
| | 17) STRETCHED FABRIC WALL SYSTEMS, |
| | SECOND FLOOR MEETING ROOM ENTRY, PLEASE |
| | EXPLAIN. |
| | 18) PLEASE PROVIDE PRODUCT APPROVALS |
| | FOR TRANSOMS 1 1/2 HOUR LABELED |
| | PERFORATED METAL INFILL PANELS. |
| | 19) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION FOR CEILINGS, |
| | WALLS, AND FLOORS. ALSO FLAME SPREAD |
| | INFORMATION REQUIRED FOR ANY CURTAINS, |
| | ETC. |
| | 20) PLEASE INDICATE TACTILE SIGNAGE FOR |
| | EXIT DOORS. |
| | 21) WHY ARE THERE NO FIRE ALARM |
| | EQUIPMENT WITHIN TRANSFORMER ROOM. |
| | 22) PLEASE INDICATE WHAT THE EMERGENCY |
| | VOICE EVACUATION MESSAGE WILL SAY. |
| | 23) ALL HOODS USED FOR THE COOKING THAT |
| | PRODUCES SMOKE OR GREASE LADEN VAPORS |
| | ARE TO BE CONNECTED TO THE BUILDING'S |
| | FIRE ALARM SYSTEM. |
| | 24) NO SPEAKER STROBES NOTED IN LOADING |
| | DOCK W-07. |
| | 25) STORAGE ROOM 2E-30 HAS NO SMOKE |
| | DETECTOR IN IT LIKE OTHER ONES. |
| | 26) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR THE INSTALLATION OF THE FIRE ALARM |
| | SYSTEM. |
| | 27) GAS INSTALLATION TO COMPLY WITH |
| | NFPA 54. PLEASE NOTE THIS ON THE |
| | DRAWINGS. |
| | 28) WHY ARE CO2 EXTINGUISHERS PLANNED |
| | FOR SOME SECTIONS INSTEAD OF ABC TYPES. |
| | 29) 8" FIRE LINE SHOWN RUN UNDERFLOOR |
| | IS NOT ALLOWED TO BE INSTALLED IN THIS |
| | MANNER. |
| | 30) PLEASE SHOW DRAFT CURTAINS AND |
| | CLOSELY SPACED FIRE SPRINKLER HEADS |
| | TO PROTECT ESCALATOR OPENINGS. |
| | 31) NO FIRE SPRINKLER PROTECTION SHOWN |
| | FOR BANQUET STORAGE 2W-14. |
| | 32) THIS OFFICE WOULD ENCOURAGE THE USE |
| | OF A COMPLETE WET PIPE FIRE SPRINKLER |
| | SYSTEM FOR THE BUILDING INSTEAD OF SOME |
| | AREAS HAVING PRE-ACTION SYSTEMS DUE |
| | TO FUTURE MAINTENANCE ISSUES. |
| | 33) FIRE MARSHAL SPELLED INCORRECTLY |
| | ON SIGN DRAWINGS ON G3.1.0. |
| | 34) PLEASE PROVIDE A TYPICAL ARRANGEMENT |
| | FOR THE EXHIBIT HALL. |
| | 35) PLEASE CLEARLY IDENTIFY EMERGENCY |
| | LIGHT FIXTURES IN 1E-36 AND EXHIBITION |
| | HALL. |
| | 36) FIRE SPRINKLER PROTECTION REQUIRED |
| | IN FIRE PUMP ROOM. |
| | 37) A HOSE CABINET IS SHOWN IN STORAGE |
| | ROOM 1N-48. |
| | 38) HOW DOES THE EXIT DOORS, SOUTH ENTRY |
| | LOBBY WORK WHEN PHASE TWO IS STARTED. |
| | 39) ARE THERE ANY FOOD SERVICE DEVICES |
| | PLANNED FOR THE EXHIBITION HALL THAT |
| | WOULD PRODUCE SMOKE OR GREASE LADEN |
| | VAPORS. IF THEY DO COMPLIANCE WITH |
| | NFPA 96 WOULD BE REQUIRED IN THE |
| | CONCESSION AREAS. |
| | 40) AFTER ANOTHER REVIEW OF THE |
| | EXHIBITION HALL IT WOULD APPEAR THAT |
| | ADDITIONAL EXIT SIGNAGE IS NEEDED ON THE |
| | WEST SIDE OF IT. |
| | 41) SMOKE EVACUATION SYSTEM CALCULATION |
| | FOR TOTAL VOLUME IS INCORRECT. BASED |
| | ON INFORMATION SUPPLIED, IT SHOULD |
| | READ 1,975,868 INSTEAD OF 1,975,328. |
| | 42) HOW WILL THE SMOKE EVACUATION |
| | SYSTEM BE IMPACTED FOR PHASE ONE, WHEN |
| | THE FUTURE PHASE TWO CONSTRUCTION IS |
| | FINISHED. |
| | 43) PLEASE DEFINE "OPERATOR" WHO WILL |
| | BE CAPABLE OF OVERRIDING THE SYSTEM AND |
| | PLACING THE SYSTEM INTO ANY MODE AT |
| | ANY TIME. |
| | 44) PLEASE EXPLAIN WHY NO MANUAL |
| | OPERATION WILL CAUSE THE SMOKE EXHAUST |
| | SYSTEM TO OPERATE. |
| | 45) THE BUILDING MANAGEMENT SYSTEM SHALL |
| | NOT BE CAPABLE OF EVER OVERRIDING THE |
| | REQUIRED FIRE ALARM SYSTEM OR SMOKE |
| | EXHAUST SYSTEM FOR THE ATRIUM. |
| | 46) RECENTLY, IT WAS EXPLAINED THAT |
| | EXHUAST FANS ARE PLANNED FOR THE EXHIBIT |
| | HALL. WILL THESE DEVICES BE ABLE TO BE |
| | BUMPED ON BY FIRE RESCUE TO EXHAUST |
| | SMOKE OR POSSIBLE PYROTECNIC RESIDUE IF |
| | APPROVED BY FIRE RESCUE. |
| | 47) PLEASE INDICATE WHAT THE WARNING |
| | SIGNAGE FOR THE CHILLER PLANT WILL SAY |
| | AND WHAT LOCATIONS WILL THEY BE PLACED. |
| | 48) NO FIRE SEPARATION SHOWN ON WALL |
| | BETWEEN LOADING DOCK AND WEST WALL |
| | OF EXHIBIT HALL. ALSO THE SECOND FLOOR |
| | SAME LOCATION. SOUTH WALL ALSO. |
| | 49) PLEASE EXPLAIN SIDELIGHTS SHOWN FOR |
| | WALLS ON A5-1.1. |
| | 50) HOW IS EXITING GOING TO BE DEFINED |
| | FROM THE ASSEMBLY TO THE LOADING DOCK |
| | AREA. |
| | |
| | MIKE CARSILLO, CAPTAIN |
| | 659-8096,EXT.8497 |
| | 835-2910 |