Plan Review Notes
Plan Review Notes For Permit 01071485
Permit Number 01071485
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-14 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT GFI PROTECTION
 OF MAINS ARE NOT SHOWN. PER 230-95
 PLEASE SHOW ON RISER LINE DIAGRAM AND
 PANEL SCHEDULES FOR MSB`S.
  
 2)NOTE: PLEASE PROVIDE CLARIFICATION
 FOR MEANS OF DISCONNECT FOR FIRE PUMP.
 FEED IS SHOWN FROM FPL TO ATS W/ NO
 MAIN OR OCP? PLEASE CALRIFY. 695-3-A-1,
 230-2, 230-72B, 695-4-B-2
  
 3)NOTE: PLEASE SUBMIT CLARIFICATION FOR
 MEANS OF SHUTTING DOWN OF GENERATOR?
 MEANS OF DISCONNECT TO BE GROUPED W/
 MAINS PER 230-72, 230-76,230-79 AND
 MARKED PER 230-2.
  
 4)NOTE: PLEASE NOTE THAT OUTLET SPACING
 TO MEET LOCAL AMENDMENST PER 210-50.
 PLEASE NOTE SOME LOCATIONS MISSING
 OUTLETS. STARTING ON E2.101 (IN-21),,,,,
  
 5)NOTE: PLEASE PLACE DETAIL ON LINE
 DIAGRAM FOR COLOR CODING OF FEEDERS
 PER LOCAL COUNTY-WIDE AND CITY-WIDE
 ADMINISTRATIVE CODE. ART215
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372