| | BUILDING COMMENTS |
| | ----------------- |
| | |
| | 1] |
| | PLEASE ADDRESS COMMENTS #S,6,7 AND 8 |
| | FROM THE FIRE REVIEW LIST. |
| | 2] |
| | PROVIDE SIGNED AND SEALED FIRE |
| | SPRINKLER LAYOUT BY THE DESIGN |
| | PROFESSIONAL. |
| | 3] |
| | WILL GUTTER SYSTEM BE PROVIDED FROM |
| | PITCHED ROOF PORTION OF THE DRIVE-UP |
| | ENTRY CANOPY. |
| | 4] |
| | SUBMIT SPECIFICATIONS FOR THE 2-HR |
| | RATED FIRE SHUTTER AT BOARD ROOM. |
| | 5] |
| | HAVE DESIGN ENGINEER LIST ON HIS |
| | DRAWINGS ALL POSITIVE AND NEGATIVE |
| | PRESSURES FOR ALL EXTERIOR OPENINGS. |
| | SUBMIT APPROVED TEST REPORTS FOR ALL |
| | EXTERIOR GLAZING AND DOORS. SHALL |
| | COMPLY WITH BOTH WIND LOADING AND |
| | IMPACT RESISTANCE. |
| | 6] |
| | PROVIDE 2HR RATED WALL SEPERATING THE |
| | CHILLER PLANT FROM THE UNDERSIDE OF THE |
| | EXTERIOR STAIRCASE. SH. A1-5.1. |
| | 7] |
| | DOOR SCHEDULES, PROVIDE SPECIFICATIONS |
| | ON THE HARDWARE GROUPS. SH8-1.1 AND 1.2 |
| | 8] |
| | PLEASE SHOW COMPLIANCE WITH SBC |
| | 705.2.2, SHAFT ENCLOSURES FOR |
| | ESCALATORS. |
| | 9] |
| | ATRIUMS, SBC 414.6 SMOKE DETECTORS AND |
| | 414.10 INTERIOR FINISH, PLEASE IDENTIFY |
| | COMPLIANCE. |
| | 10] |
| | SBC 1004.3.5, IDENTIFY AREAS OF REFUGE. |
| | 11] |
| | SBC 1007.3, ALL STAIRWAYS SHALL COMPLY |
| | WITH THE RISE AND RUN RATIO. |
| | 12] |
| | PLEASE COMPLETE THE SUBMITTED FLA. |
| | ENERGY FORMS. OWNER SHALL SIGN,AND ALL |
| | 9 SETS SUBMITTED ARE FOR THE SAME AREA |
| | OF THE BUILDING??? |
| | 13] |
| | EXIT AT LOADING DOCK AREA IS TO BE |
| | CLEARLY MARKED WITH SIGNS AND PATH OF |
| | TRAVELIDENTIFIED. |
| | 14] |
| | SHEET A1-5.2, EXPLAIN 2HR RATING BEHIND |
| | INTERIOR OFFICES AT KITCHEN AREA. |
| | |
| | PLEASE SEE ADDITIONAL COMMENTS PROVIDED |
| | FOR ACCESSIBILITY COMPLIANCE. |
| | SEPERATE PACKAGE SHEETS,1 THRU 9. |
| | |
| | |
| | PLAN REVIEWER: |
| | LUIS MARTINEZ |
| | 561-659-8096 |
| | #8456 |