Plan Review Notes
Plan Review Notes For Permit 01071485
Permit Number 01071485
Review Stop B
Sequence Number 1
Notes
Date Text
2001-09-12 00:00:00 
 BUILDING COMMENTS
 -----------------
  
 1]
 PLEASE ADDRESS COMMENTS #S,6,7 AND 8
 FROM THE FIRE REVIEW LIST.
 2]
 PROVIDE SIGNED AND SEALED FIRE
 SPRINKLER LAYOUT BY THE DESIGN
 PROFESSIONAL.
 3]
 WILL GUTTER SYSTEM BE PROVIDED FROM
 PITCHED ROOF PORTION OF THE DRIVE-UP
 ENTRY CANOPY.
 4]
 SUBMIT SPECIFICATIONS FOR THE 2-HR
 RATED FIRE SHUTTER AT BOARD ROOM.
 5]
 HAVE DESIGN ENGINEER LIST ON HIS
 DRAWINGS ALL POSITIVE AND NEGATIVE
 PRESSURES FOR ALL EXTERIOR OPENINGS.
 SUBMIT APPROVED TEST REPORTS FOR ALL
 EXTERIOR GLAZING AND DOORS. SHALL
 COMPLY WITH BOTH WIND LOADING AND
 IMPACT RESISTANCE.
 6]
 PROVIDE 2HR RATED WALL SEPERATING THE
 CHILLER PLANT FROM THE UNDERSIDE OF THE
 EXTERIOR STAIRCASE. SH. A1-5.1.
 7]
 DOOR SCHEDULES, PROVIDE SPECIFICATIONS
 ON THE HARDWARE GROUPS. SH8-1.1 AND 1.2
 8]
 PLEASE SHOW COMPLIANCE WITH SBC
 705.2.2, SHAFT ENCLOSURES FOR
 ESCALATORS.
 9]
 ATRIUMS, SBC 414.6 SMOKE DETECTORS AND
 414.10 INTERIOR FINISH, PLEASE IDENTIFY
 COMPLIANCE.
 10]
 SBC 1004.3.5, IDENTIFY AREAS OF REFUGE.
 11]
 SBC 1007.3, ALL STAIRWAYS SHALL COMPLY
 WITH THE RISE AND RUN RATIO.
 12]
 PLEASE COMPLETE THE SUBMITTED FLA.
 ENERGY FORMS. OWNER SHALL SIGN,AND ALL
 9 SETS SUBMITTED ARE FOR THE SAME AREA
 OF THE BUILDING???
 13]
 EXIT AT LOADING DOCK AREA IS TO BE
 CLEARLY MARKED WITH SIGNS AND PATH OF
 TRAVELIDENTIFIED.
 14]
 SHEET A1-5.2, EXPLAIN 2HR RATING BEHIND
 INTERIOR OFFICES AT KITCHEN AREA.
  
 PLEASE SEE ADDITIONAL COMMENTS PROVIDED
 FOR ACCESSIBILITY COMPLIANCE.
 SEPERATE PACKAGE SHEETS,1 THRU 9.
  
  