| Plan Review Notes For Permit 01071410 |
| Permit Number |
01071410 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-05 00:00:00 | **************** UNSAT **************** | | | | | | PLEASE NOTE THAT NOT ALL NOTES FROM | | | FIRST REVIEW WERE ADDRESSED. | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2)NOTE: PLEASE NOTE LOAD FOR AHU IS NOW | | | SHOWN AT 10KW AND IS SHOWN AT 5KW PER | | | PHASE ON PANEL SCHEDULE. PLEASE NOTE | | | THAT LOAD FOR RANGE IS ALSO SHOWN AT | | | 5KW PER PHASE ON SCHEDULE BUT STILL | | | SHOWN AT 5KW ON LOAD CALCUALTIONS?? | | | PLEASE ALSO NOTE SAME FOR OTHER 2-POLE | | | LOADS/ PLEASE CORRELATE. | | | | | | 3)NOTE: PLEASE NOTE LOAD FOR WATER PUMP | | | SHOWN AT 4.5KW AND 4KW? WHICH ONE? | | | | | | 4)NOTE: PLEASE NOTE MISSING COLD WATER | | | PIPE AS PART OF THE GROUNDING ELECTRODE | | | SYSTEM PER 250-50. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|