| 2001-08-30 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | SBC 104.2.2 |
| | |
| | 1. PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2. BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH CO.,THE PERMIT PLANS STAMPED |
| | BY THEM AND THE RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. |
| | |
| | 3. FLORIDA ENERGY EFFICIENCY CODE FORM |
| | MUST BE SIGNED BY OWNER/AGENT & DATED |
| | AS REQUIRED BY THE 1997 FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILDING |
| | CONSTRUCTION. |
| | |
| | 4. IN ADDITION TO SIGNING, SEALING AND |
| | DATING EACH PAGE OF THE PLANS, THE |
| | ENGINEER IN RESPONSIBLE CHARGE MUST |
| | LEGIBLY INDICATE IN A TITLE BLOCK THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON |
| | EACH PLAN SHEET. 61G15-23.002 F.A.C. |
| | |
| | 5.PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | GLASS BLOCK |
| | |
| | 6. PROVIDE SOIL TEST PER SEC. 1804.2.2 |
| | OF CITY AMENDMENTS TO 1997 SBC. |
| | |
| | 7. TRUSS ENGINEERED DRAWINGS SUBMITTED |
| | MUST BE SIGNED & SEALED BY TRUSS MFGR'S |
| | ENGINEER AND APPROVED BY ARCHITECT OF |
| | RECORD. |
| | |
| | 8. PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. PRODUCT |
| | APPROVAL SUBMITTALS ARE NOT MARKED WITH |
| | METHOD OF ATTACHMENT. |
| | |
| | 9. SUBMIT DESIGN CERTIFICATION FORM |
| | SIGNED & SEALED BY ENGINEER OR ARCHITECT |
| | OF RECORD. FORM ATTACHED. |
| | |
| | 10.PLANS DO NOT SHOW WIND PRESSURE OF |
| | OPENINGS (WINDOWS & DOORS). |
| | |
| | |