Plan Review Notes
Plan Review Notes For Permit 01071410
Permit Number 01071410
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 5)NOTE: PLEASE SHOW A/C COND DISCONNECT
 PER 440-11.
  
 6)NOTE: PLEASE NOTE THAT LOAD SHOWN FOR
 LAUNDRY CIRCUIT IS TWICE THAN REQ`D?
 PLEASE CLARIFY.
  
 7)NOTE: PLEASE CLARIFY RANGE SHOWN AT
 8KW ON PANEL AND 5KW ON LOAD CALCULATION
 -S.??
  
 8)NOTE: PLEASE CLARIFY AHU HEAT LOAD
 SHOWN AT 5KW?PLEASE DOUBLE CHECK
 SIZE FOR A HOUSE THIS SIZE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372