| Plan Review Notes For Permit 01071410 |
| Permit Number |
01071410 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-08 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 3) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 4) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | | | | 5)NOTE: PLEASE SHOW A/C COND DISCONNECT | | | PER 440-11. | | | | | | 6)NOTE: PLEASE NOTE THAT LOAD SHOWN FOR | | | LAUNDRY CIRCUIT IS TWICE THAN REQ`D? | | | PLEASE CLARIFY. | | | | | | 7)NOTE: PLEASE CLARIFY RANGE SHOWN AT | | | 8KW ON PANEL AND 5KW ON LOAD CALCULATION | | | -S.?? | | | | | | 8)NOTE: PLEASE CLARIFY AHU HEAT LOAD | | | SHOWN AT 5KW?PLEASE DOUBLE CHECK | | | SIZE FOR A HOUSE THIS SIZE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|